4 leds, 5 configuration, 3modbus/tcp - data areas – Pilz PNOZ mmc1p ETH User Manual
Page 17: 4 assignment of data areas
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
3-7
3.4
Assignment of data areas
3
Modbus/TCP - Data areas
3.4.4
LEDs
LEDs
3-
ModbusTCP_Datenbereiche-LEDs-PNOZmulti
The table below describes the Modbus/TCP data areas that contain the
LED status.
Relevant areas for the data are defined in the Modbus/TCP data areas
Discrete Inputs (1x) and Input Register (3x). Read access is available to
these data areas.
Bit 0 = 1: LED OFAULT illuminates or flashes
Bit 1 = 1: LED IFAULT illuminates or flashes
Bit 2 = 1: LED FAULT illuminates or flashes
Bit 3 = 1: LED DIAG illuminates or flashes
Bit 4 = 1: LED RUN illuminates
Bit 5: Reserved
Bit 6: Reserved
Bit 7: Reserved
3.4.5
Configuration
Configuration
3-
ModbusTCP_Datenbereiche-Konfiguration-PNOZmulti
The table below describes the Modbus/TCP data areas that contain the
device data from the base unit and the project data. The data was de-
fined in the PNOZmulti Configurator.
Relevant areas for the data are defined in the Modbus/TCP data areas
Discrete Inputs (1x) and Input Register (3x). Read access is available to
these data areas.
Register
(3x)
Discrete Input
(1x)
Content
High Byte
Low Byte
520
8335...8320
8 Bit LED status;
8 Bit reserved
Reserved
PNOZmulti LEDs
521…783
Reserved
Register
(3x)
Discrete Input
(1x)
Content
High Byte
Low Byte
784
12559... 12544
Product number
HH Byte
HL Byte
785
12575... 12560
Product number
LH Byte
LL Byte
786
12591... 12576
Device version
HH Byte
HL Byte
787
12607... 12592
Device version
LH Byte
LL Byte
788
12623... 12608
Serial number
HH Byte
HL Byte
789
12639... 12624
Serial number
LH Byte
LL Byte