Assignment of data areas, 1 virtual inputs, 3modbus/tcp - data areas – Pilz PNOZ mmc1p ETH User Manual
Page 14: 4 assignment of data areas
3.4
Assignment of data areas
3
Modbus/TCP - Data areas
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
3-4
3.4
Assignment of data areas
3400
Assignment of data areas
3-
ModbusTCP_Coil and Register Map-Einleitung-PNOZmulti
Data can be accessed via various Modbus/TCP data areas.
The tables below show the relationship between Modbus/TCP data ar-
eas and the content of the data areas.
3.4.1
Virtual inputs
Virtual inputs
3-
ModbusTCP_Datenbereiche-Virtuelle Eingänge-PNOZmulti
The table below describes the Modbus/TCP data areas that contain the
current state of the virtual inputs on the PNOZmulti. These are the virtual
inputs that can be set by the user.
Relevant areas for the data are defined in each Modbus/TCP data area
(Coils (0x), Discrete Inputs (1x), Input Register (3x), Holding Register
(4x)). Read/write access will depend on the Modbus/TCP data area.
Register
(3x, 4x)
Coil/
Discrete Input
(0x, 1x)
Content
High Byte
Low Byte
0
15... 0
State of the inputs
0...15
i15…i8
i7…i0
1
31... 6
State of the inputs
16...31
i31…i24
i23…i16
2
47...32
State of the inputs
32...47
i47…i40
i39…i32
3
63...48
State of the inputs
48...63
i63…i56
i55…i48
4
79... 64
State of the inputs
64...79
i79…i72
i71…i64
5
95...80
State of the inputs
80...95
i95…i88
i87…i80
6
111...96
State of the inputs
96...111
i111…i104
i103…i96
7
127...112
State of the inputs
112...127
i127…i120
i119…i112