Page 16

background image

3.4

Assignment of data areas

3

Modbus/TCP - Data areas

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

3-6

3.4.3

Virtual outputs

Virtual outputs

3-

ModbusTCP_Datenbereiche-Virtuelle Ausgänge-PNOZmulti

The table below describes the Modbus/TCP data areas that contain the

state of the virtual outputs on the PNOZmulti.

Relevant areas for the data are defined in the Modbus/TCP data areas

Discrete Inputs (1x) and Input Register (3x). Read access is available to

these data areas.

INFORMATION

To check whether the watchdog has been triggered, set a virtual

input permanently to "1".

If this input is "0", then the watchdog has been triggered.

Register
(3x)

Discrete Input
(1x)

Content

High Byte

Low Byte

512

8207...8192

State of the outputs
0...15

o15…o8

o7…o0

513

8223...8208

State of the outputs
16...31

o31…o24

o23…o16

514

8239...8224

State of the outputs
32...47

o47…o40

o39…o32

515

8255...8240

State of the outputs
48...63

o63…o56

o55…o48

516

8271...8256

State of the outputs
64...79

o79…o72

o71…o64

517

8287...8272

State of the outputs
80...95

o95…o88

o87…o80

518

8303...8288

State of the outputs
96...111

o111…o104

o103…o96

519

8319...8304

State of the outputs
112...127

o127…o120

o119…o112