3 virtual outputs, 3modbus/tcp - data areas, 4 assignment of data areas – Pilz PNOZ mmc1p ETH User Manual
Page 16
3.4
Assignment of data areas
3
Modbus/TCP - Data areas
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
3-6
3.4.3
Virtual outputs
Virtual outputs
3-
ModbusTCP_Datenbereiche-Virtuelle Ausgänge-PNOZmulti
The table below describes the Modbus/TCP data areas that contain the
state of the virtual outputs on the PNOZmulti.
Relevant areas for the data are defined in the Modbus/TCP data areas
Discrete Inputs (1x) and Input Register (3x). Read access is available to
these data areas.
INFORMATION
To check whether the watchdog has been triggered, set a virtual
input permanently to "1".
If this input is "0", then the watchdog has been triggered.
Register
(3x)
Discrete Input
(1x)
Content
High Byte
Low Byte
512
8207...8192
State of the outputs
0...15
o15…o8
o7…o0
513
8223...8208
State of the outputs
16...31
o31…o24
o23…o16
514
8239...8224
State of the outputs
32...47
o47…o40
o39…o32
515
8255...8240
State of the outputs
48...63
o63…o56
o55…o48
516
8271...8256
State of the outputs
64...79
o79…o72
o71…o64
517
8287...8272
State of the outputs
80...95
o95…o88
o87…o80
518
8303...8288
State of the outputs
96...111
o111…o104
o103…o96
519
8319...8304
State of the outputs
112...127
o127…o120
o119…o112