Hanna Instruments HI 8050 User Manual
Page 8

8
panel C19
C19
C19
C19
C19 (SECTOR ACCUMUL). In addition, this panel displays the
valve number assigned with the corresponding sector.
Accumulations erase mode can be chosen on panel S65
S65
S65
S65
S65 (ERASE STATIS-
TICS). The accumulation erase can be performed for all programs and
sectors using one of the following ways:
- Manually
- Every day at specified hour
- Automatically whether the accumulations counter values overflows
FERTILIZA
FERTILIZA
FERTILIZA
FERTILIZA
FERTILIZATION CONTROL
TION CONTROL
TION CONTROL
TION CONTROL
TION CONTROL
Fertilization can be made mixing the irrigation water with 4 types of fertil-
izers from 4 tanks. Dosing of these fertilizers is controlled by conductivity
or by volume (ratiometric or volume). Volume fertilizer control mode is
available only if the program works in volume irrgation mode. In all cases
is available a correction of fertilization with temperature. The temperatures
for correction of fertilization are set in panel S44
S44
S44
S44
S44 (IRRIGATION CORR).
The type of control used for fertilization is selected in panel S37
S37
S37
S37
S37 (FERT
CTRL MODE):
•
CONDUCTIVITY CONTROL
CONDUCTIVITY CONTROL
CONDUCTIVITY CONTROL
CONDUCTIVITY CONTROL
CONDUCTIVITY CONTROL
Conductivity control is used to control fertilization based on the conduc-
tivity of irrigation water. A reference for the conductivity is set in S38
S38
S38
S38
S38 (EC
CONTROL) and a prescription for the proportion of fertilizers is set in S39
S39
S39
S39
S39
(SET FERTILIZERS) and the controller will dose the prescribed proportion of
fertilizers in such a manner to keep the EC water within specified range:
EC refernce minus or plus minimum and maximum offset values. In addi-
tion to this mode a differential conductivity control is available (set in S40
S40
S40
S40
S40
(EC DIFF CTRL CFG). In this mode the controller will dose the fertilizers in
a way that the irrigation water will have the conductivity of reference added
with the conductivity of input water. In this way the amount of fertilizer
dosed is the same even if the input water is contaminated with some sub-
stances that produce the rising of EC. Conductivity sensor status and
conductivity reference are displayed on panel C06
C06
C06
C06
C06 (EC STATE). In addi-
tion, the conductivity sensor value is displayed on panels C01
C01
C01
C01
C01 (GEN-
ERAL INFO) and C03
C03
C03
C03
C03 (SENSORS STATE). Temperature reference correc-
tion and input EC are displayed on panel C12
C12
C12
C12
C12 (EC CORRECTION).
The conductivity control is made in accordance with a preset conductivity
reference value, specific for each irrigation program. In addition, the con-
ductivity reference has a proportional band and a dead band that can be
set using panel S38(EC CONTROL). If the difference between setpoint and
the EC of the water is greater than the dead band for a period of time an