I.lon 100 rni limits, I.lon 100 application limits, I.lon 100 rni limits -5 – Echelon i.LON 100 e2 Internet Server User Manual
Page 13: I.lon 100 application limits -5
![background image](/manuals/735740/13/background.png)
i.LON 100 Internet Server User’s Guide
1-5
i.LON 100 RNI Limits
The capabilities of the RNI on the i.LON-100 are in largely dependent on the
software running on the host computer. When used as an LNS network
interface, the i.LON-100 RNI has the following limits (see the Introduction to
LonWorks document or the LonMaker User’s Guide for more information about
these limits):
• Up to 32768 address table entries.
• Up to 15 simultaneous transactions.
• Up to 1096 aliases.
• Up to 15 groups.
• Up to 4096 dynamic network variables.
i.LON 100 Application Limits
The i.LON 100 application has the following limits:
• Up to 4096 address table entries.
• Up to 32 simultaneous transactions.
• Up to 1024 aliases.
• The i.LON 100 application theoretically supports up to 3000 dynamic
network variables, but the i.LON 100 will run out of memory before this limit
is reached; the practical limit depends on the sizes of the defined dynamic
network variables. You can check the available memory on the System Info
Web page.