Table 3 - Condenser Physical Data

Unit Size

30HH015

30HH020

30HH025

30HH030

30HH045

30HH055

30HH065

Condensers (No.)

1

2

2

2

3

2

2

Condenser Type

Shell-and-Coil

Sheil-anc -Tube

Tubes or Coils, each

6

4

1 - 6

1 - 4

6

6

64

64

Effective External Surface, each (sq ft)

82.7

53.9

1 - 5 3 . 9
1 - 82.7

82.7

82.7

165.7

165.7

Water Side Volume, each (gal)

3.5

2.5

1 - 2.5

1 - 3.5

3.5

3.5

5.0

5.0

Nominal Shell Diam (in.)

10-15/16

10-15/16

10-15/16

10-15/16

10-15/16

10-3/4

10-3/4

Shell Length (in.)

42-5/8

34-5/8

1 - 34-5/8
1 - 42-5/8

42-5/8

42-5/8

77

77

Water Connections (Total No.)

2

4

4

4

2

4

3

Water Connection

Inlet

1 - 2"

2 - 1-1/2”

1 - 1-1/2”
1 - 2"

2 - 2"

3 - 2"

2 - 2"

1 - 3"

Size (each cond. )

Outlet

1 - 2"

2 - 1-1/2"

1 - 1-1/2"
1 - 2"

2 - 2”

3 - 2"

2 - 1-1/2"

2 - 2”

Coil or Tube Type

Trufin

Trufin

Coil or Tube OD (in.)

7/8

3/4

Nominal Shell Thickness (in.)

.278

.307

Materials

Shell

Steel

Steel

of

Coil or Tubes

Copper

Copper

Construction

Tube Sheet

Steel

Steel

Max. Design

Water Side

100

100

Working Press, (psig)

Refrig. Side

385

385

Г'

NOTE: The 30HH065 unit is supplied with two subcooiers (one per circuit) to provide 15 F of subcooling.