beautypg.com

Liquid charging method, Oil charge, To add oil – Carrier 30HH User Manual

Page 21: To remove oil, Check the controls expansion valve, Safety thermostat adjustment, 30hh,hj, Carrier, Installation

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Carrier

INSTALLATION

30HH,HJ

Liquid Charging Method

Liquid charge the units thru the condenser liquid
line shut-off valves.

1. Backseat condenser liquid line shut-off valve.

2.

Connect a refrigerant cylinder loosely to the

gage connection of the condenser liquid line
shut-off valve. Purge the charging line and
tighten the connections.

3. Weigh the refrigerant cylinder (if possible).

4. Front seat the condenser liquid shut-off valve.

5.

if the system has been dehydrated and is

under

vacuum,

break

vacuum

with

refriger­

ant

(Gas

charge).

Build

system

pressure

to

58 psi for R 22 (32 F). Invert refrigerant
cylinder

so

that

liquid

refrigerant

will

be

charged.

6.

Allow the compressor to cycle on the low

pressure

cut-out

until

sufficient

pounds

of

refrigerant have been added (Table 6).

7.

When the unit is sufficiently charged, close

the

cylinder

valve,

backseat

the

liquid

line

shut-off valve, and remove the charging ap­

paratus. Replace the cap in the liquid line

shut-off valve.

NOTE: Where it is impossible to weigh
the refrigerant cylinder, the initial re­
frigerant

charge

must

be

an

approxi­

mation. After it has been added, back­

seat the liquid line shut-off valve and

allow the unit to operate. A clear flow
of liquid in the liquid-moisture indica­
tor, indicates a satisfactory charge.

If the charge is not sufficient, add re­

frigerant until a clear flow of liquid

show in the glass.

CAUTION: Be careful not to overcharge
the system. Overcharging results in:

(a) Higher discharge pressure with

higher cooling water consumption.

(b) Possible compressor damage.

(c) Higher power consumption.

OIL CHARGE

The 30HH,HJ units are charged with oil at the

factory (Table 2). Because of added piping with

evaporative condenser models, it may be neces­
sary to add oil at the job site. Observe the oil
level closely at startup and add oil, if required,
to bring the level in the crankcase to the middle
of the bull's-eye during steady operation.

To Add Oil

1.

Close suction shut-off valve and pump down

crankcase

to

2

psig.

(Low

pressure

cut-out

must be shorted.) Wait a few minutes and
repeat

as

needed

until

pressure

remains

at

2 psig.

2.

Remove oil fill plug to the right of the bull's-

eye and add oil thru plug hole.

3. Replace plug.

4.

Run compressor for about 20 minutes and

check the oil level.

CAUTION: To insure trouble free oper­
ation, use only Carrier approved com­
pressor oil, Specification No. PP-33-2.
Do not re-use oil that has been drained
out, or oil that has been left open to the
atmosphere.

To Remove Oil

1. Pump down compressor to 2 psig gage.

2.

Loosen

the

1/4”

pipe plug in compressor

base and allow the oil to seep out past the
threads of the plug.

CAUTION: The crankcase will be under

slight pressure. Be careful not to re­
move the plug; the entire oil
may be lost.

charge

CHECK THE CONTROLS

Expansion Valve

The

thermal

expansion

valves

control

the

flow

of

liquid

refrigerant

by

maintaining

constant

superheat of the vapor leaving the cooler. They
are pre-set at the factory to maintain a super­
heat of 8 F. Do not attempt to adjust them unless
you are certain it is absolutely necessary.

Safety Thermostat Adjustment

The safety thermostat is of non-cycling, manual
reset type. It has an adjusting dial with a stop
set at 36 F for normal chilled water applica­
tions, but can be readjusted for a lower stop if

21