Liquid charging method, Oil charge, To add oil – Carrier 30HH User Manual
Page 21: To remove oil, Check the controls expansion valve, Safety thermostat adjustment, 30hh,hj, Carrier, Installation
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Carrier
INSTALLATION
30HH,HJ
Liquid Charging Method
Liquid charge the units thru the condenser liquid
line shut-off valves.
1. Backseat condenser liquid line shut-off valve.
2.
Connect a refrigerant cylinder loosely to the
gage connection of the condenser liquid line
shut-off valve. Purge the charging line and
tighten the connections.
3. Weigh the refrigerant cylinder (if possible).
4. Front seat the condenser liquid shut-off valve.
5.
if the system has been dehydrated and is
under
vacuum,
break
vacuum
with
refriger
ant
(Gas
charge).
Build
system
pressure
to
58 psi for R 22 (32 F). Invert refrigerant
cylinder
so
that
liquid
refrigerant
will
be
charged.
6.
Allow the compressor to cycle on the low
pressure
cut-out
until
sufficient
pounds
of
refrigerant have been added (Table 6).
7.
When the unit is sufficiently charged, close
the
cylinder
valve,
backseat
the
liquid
line
shut-off valve, and remove the charging ap
paratus. Replace the cap in the liquid line
shut-off valve.
NOTE: Where it is impossible to weigh
the refrigerant cylinder, the initial re
frigerant
charge
must
be
an
approxi
mation. After it has been added, back
seat the liquid line shut-off valve and
allow the unit to operate. A clear flow
of liquid in the liquid-moisture indica
tor, indicates a satisfactory charge.
If the charge is not sufficient, add re
frigerant until a clear flow of liquid
show in the glass.
CAUTION: Be careful not to overcharge
the system. Overcharging results in:
(a) Higher discharge pressure with
higher cooling water consumption.
(b) Possible compressor damage.
(c) Higher power consumption.
OIL CHARGE
The 30HH,HJ units are charged with oil at the
factory (Table 2). Because of added piping with
evaporative condenser models, it may be neces
sary to add oil at the job site. Observe the oil
level closely at startup and add oil, if required,
to bring the level in the crankcase to the middle
of the bull's-eye during steady operation.
To Add Oil
1.
Close suction shut-off valve and pump down
crankcase
to
2
psig.
(Low
pressure
cut-out
must be shorted.) Wait a few minutes and
repeat
as
needed
until
pressure
remains
at
2 psig.
2.
Remove oil fill plug to the right of the bull's-
eye and add oil thru plug hole.
3. Replace plug.
4.
Run compressor for about 20 minutes and
check the oil level.
CAUTION: To insure trouble free oper
ation, use only Carrier approved com
pressor oil, Specification No. PP-33-2.
Do not re-use oil that has been drained
out, or oil that has been left open to the
atmosphere.
To Remove Oil
1. Pump down compressor to 2 psig gage.
2.
Loosen
the
1/4”
pipe plug in compressor
base and allow the oil to seep out past the
threads of the plug.
CAUTION: The crankcase will be under
slight pressure. Be careful not to re
move the plug; the entire oil
may be lost.
charge
CHECK THE CONTROLS
Expansion Valve
The
thermal
expansion
valves
control
the
flow
of
liquid
refrigerant
by
maintaining
constant
superheat of the vapor leaving the cooler. They
are pre-set at the factory to maintain a super
heat of 8 F. Do not attempt to adjust them unless
you are certain it is absolutely necessary.
Safety Thermostat Adjustment
The safety thermostat is of non-cycling, manual
reset type. It has an adjusting dial with a stop
set at 36 F for normal chilled water applica
tions, but can be readjusted for a lower stop if
21