30HH,HJ
MAINTENANCE
Carrier
TROUBLE DIAGNOSIS CHART
SYMPTOMS
CAUSE
REMEDY
A. Compressor does
not run
Power line open
Reset circuit breaker
Control circuit fuse blown
Check
control
circuit
for
ground
or short, repair and replace fuse
Safety thermostat tripped
Reset thermostat
Tripped starter overloads
See
starters
and
overloads
(check
the controls)
Condenser
circulating
pump
not running
Power off - restart
Pump binding - free pump
Incorrect wiring - rewire
Pump motor burned out - replace
Control stuck open
Loose terminal connection
Improperly wired controls
Low line voltage
Compressor motor effective
Seized compressor
Replace control
Check connections
Check wiring and rewire
Check line voltage - determine
location of voltage drop
Check motor winding for open or short.
Replace compressor, if necessary
Replace compressor
B. Compressor cycles on
low pressure control
Low
pressure
control
erratic in action
Raise differential setting
Check capillary for pinches
Replace control
Compressor
suction
valve
leaking
Replace valve plate
Compressor
suction
shut-off
valve partially closed
Open valve
Low refrigerant charge
Add refrigerant
Plugged
compressor
suction
strainer
Clean strainer
C . Compressor cycles on
high pressure control
High
pressure
control
erratic in action
Check
capillary
tube
for
pinches
Set control as required
Compressor
discharge
valve
partially closed
Open valve
Air in system
Purge
40