MAINTENANCE

Carrier

TROUBLE DIAGNOSIS CHART

SYMPTOMS

CAUSE

REMEDY

A. Compressor does

not run

Power line open

Reset circuit breaker

Control circuit fuse blown

Check

control

circuit

for

ground

or short, repair and replace fuse

Safety thermostat tripped

Reset thermostat

Tripped starter overloads

See

starters

and

overloads

(check

the controls)

Condenser

circulating

pump

not running

Power off - restart

Pump binding - free pump

Incorrect wiring - rewire

Pump motor burned out - replace

Control stuck open

Loose terminal connection

Improperly wired controls

Low line voltage

Compressor motor effective

Seized compressor

Replace control

Check connections

Check wiring and rewire

Check line voltage - determine

location of voltage drop

Check motor winding for open or short.

Replace compressor, if necessary

Replace compressor

B. Compressor cycles on

low pressure control

Low

pressure

control

erratic in action

Raise differential setting

Check capillary for pinches

Replace control

Compressor

suction

valve

leaking

Replace valve plate

Compressor

suction

shut-off

valve partially closed

Open valve

Low refrigerant charge

Add refrigerant

Plugged

compressor

suction

strainer

Clean strainer

C . Compressor cycles on

high pressure control

High

pressure

control

erratic in action

Check

capillary

tube

for

pinches

Set control as required

Compressor

discharge

valve

partially closed

Open valve

Air in system

Purge

40