beautypg.com

High and low pressure controls, 30hh,hj, Installation – Carrier 30HH User Manual

Page 22

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

30HH,HJ

INSTALLATION

glycols or brines are to be cooled. The adjust­

ment tolerance is commonly j- 1 F.

DAMAGE DUE TO THE FREEZING OF A CHILL -
ER IS NOT COVERED BY THE WARRANTY.

The

safety

thermostat

bulb

is

located

in

the

leaving chilled water piping stubout.

IMPORTANT:

This

thermostat

should

be checked at the time of installation
and at least once every season. If the
bulb is damaged in handling, its cali­
bration may be off.

To check the safety thermostat:

1.

Place the thermal bulb in a vacuum bottle

filled with water and add crushed ice.

NOTE: This is an insert type bulb. On

earlier units, removal opens water sys-
except on 30HH,HJ045 thru 065 units
which use a sealed well. Later units
all use a sealed well.

2.

Stir

the

contents with

a thermometer and

note the temperature at which safety thermo­
stat cuts out.

3.

Reset the safety thermostat if necessary. To

set the control, use screwdriver in slot and
rotate

dial

until

the

desired

temperature

at

which compressor is to stop is directly under
indicator "B”.

To recalibrate the safety thermostat;

1.

Measure the temperature as close to the bulb

as

possible,

immediately

after

the

compres­

sor stops.

2.

Break the painted seal between the dial and

the adjusting plate with a knife.

3.

Carefully loosen the two dial screws. Be care­

ful not to turn the brass cylinder below the
dial during this or any of the following oper­
ations.

4.

Turn the dial ONLY so that the fixed indica­

tor

points

to

thè

temperature

measured

at

step 1.

5. Carefully tighten the dial screws.

I ‘-f

FIXED IMDICATOR

ADJUSTING SLOT

Fig. 27 - Safety Thermostat

High and Low Pressure Controls

Pressure control settings are shown in Table 8.

The 30HJ high pressure control settings are suit­
able for use with either air-cooled or evaporative
condensers. The control setting (Table 8) is a
fixed setting and is nonadjustable.

Check the high pressure switch setting by slowly
closing the discharge shut-off valve. The com­

pressor

should

shut

down

when

the

discharge

pressure reaches 260 or 355 psi (as required)

and start up when the pressure drops to 210, or
255 psi (as required).

The 30HH high pressure switches are adjustable
and equipped with a stop to prevent field setting
above 280 lbs.

To

check

the

low

pressure

switch,

close

the

suction shut-off valve and allow the compressor
to pump down. The compressor should cut out
when the suction pressure falls to 46 psig, and
automatically

start

up

again

when

the

suction

pressure builds up to 83 psig.

Both sides should be checked at startup and at
least once a year thereafter.

22