30HH,HJ

MAINTENANCE

Carrier

SYMPTOMS

j CAUSE

REMEDY

I. Frosted liquid line

1

Receiver shut-off valve

j partially closed or

restricted

1

Open valve or remove restriction

j

Restricted catchall

Replace

COMPRESSOR MAINTENANCE

The 30HH and H] Liquid Chillers use the Carrier

6D hermetic compressors . For detailed compres-

sor

operation

and

maintenance

instructions,

consult

the 6D-Product Information Service Manual

CAUSE AND PREVENTION OF FREEZE-UP

CAUSE

PREVENTION

Improper charging.

Make sure that a full quantity of water is flowing

through the cooler while charging.

Make sure the suction pressure in the cooler is

equal to or greater than that corresponding to 32 F

(58 psi for Refrigerant-22).

Improperly set safety thermostat

Check

the

safety

thermostat

for

proper

setting

at

the beginning of each season.

Operating with safety thermostat bypassed.

The

safety

thermostat

is

wired

in

series

with

the

compressor motor starter. Do not bypass it.

Improper chilled water circulation.

Use an ample sized cleanable strainer in the chilled

water circuit. Make certain the strainer is clean

to Insure full flow and velocity of chilled water. It

may sometimes be necessary to treat the water to

prevent formation of deposits .

Not draining for winter shutdown.

When the system is shut down for the winter, re­

move the drain plugs and drain the cooler. Blow

out any remaining water with air.

NOTES: 1. If the ambient temiperature is below 32 F, freezing can be prevented by one of two methods:

a.

Drain all water from the equipment.

b.

Add antifreeze to the water.

A safe antifreeze that meets code and Underwriter requirements may be circulated with the residual

water in the system. The antifreeze may be drained and re-used until it is diluted to the minimum

safe limit.

2. Damage to chiller due to freezing is considered abuse and is not covered by the warranty.