beautypg.com

Refrigerant piping, 30hh,hj, Carrier – Carrier 30HH User Manual

Page 15: Installation

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Carrier

INSTALLATION

30HH,HJ

REFRIGERANT PIPING

For refrigerant piping sizing refer to Part 3 -
’’Piping Design” - of the System Design Manual.

The ЗОНЫ and HJ Packaged Liquid Chillers are
leak tested at the factory and provided with a
holding charge of Refrigerant 22.

NOTE: 30HH015,020 fully charged with
R 22 at factory.

If the holding charge is still in the system upon
arrival at the erection site, the likelihood of leaks
is slight. If the unit is not under pressure, test
for leaks as outlined under Leak Testing.

NOTE: Be sure to open all stop valves

when testing for leaks.

30HJ UNIT

This section also applies to the 30HJ unit which
is to be connected to a remote condenser in the
field. Figure 19 is a typical refrigerant piping
diagram showing the 30HJ020 thru 030 unit and a
9H

Evaporative

Condenser.

Simdlar

connections

may be used for the 30Ш045 and 065 unit using
manifolded

compressors.

Figure

20-22

illus­

trate typical refrigerant piping for 30HJ020 thru

065

units

and

air-cooled

condensers.

Receivers

have been omitted, but it must be recognized
that with this arrangement the refrigerant charge
is

critical.

An

overcharged

or

undercharged

system can cause a loss of capacity. If a receiver
is

not

Included,

an

accurate

refrigerant

charge

must be maintained to assure efficient operation.

Figure 20-22 are shown to illustrate a typical
installation using 9A or 09DC016 air-cooled con­
densers. These illustrations are to be used as a
guide when designing a system and are not in­
tended to be used as an actual piping layout. Con­

sult the ’’System Design Manual” and condenser
literature before designing the actual system.

Each 30HJ unit (except -015) consists of two
independent

refrigerant

circuits.

Each

circuit

must be isolated from the other.

Discharge lines and liquid lines are shown mani­

folded at the units on 30HJ045 and 065 units to
permit a minimum amount of piping. Individual
discharge lines may be run from each compres­

sor to the condenser if desirable. Liquid lines
must be manifolded as shown to enter the 30HJ065
unit to agree with the unit refrigerant circuit. In­
dividual liquid line connections are necessary on
the 30HJ045 unit.

F R O M T A B L E - F O R V E N T I N G A S S H O W N

M U F F L E R S S H O U L D
A S P O S S I S L E .

I N S T A L L E D A S C L O S E T O T H E C O M P R E S S O ч

U N I T

“ X ” D I M . *

3 0 H U 0 1 5

6

"

3 Û H J 0 2 0

1 5 "

3 0 H J 0 2 5

1 5 "

3 0 H J 0 3 0

1 5 "

3 0 H U 0 A 5

1 5 "

3

O H J O

6 5

1 5 "

" X " D I M . - T H I S I S
T H E M I N I M U M , E L E V A T I O N
R E Q U I R E D B E T W E E N A
C O N D E N S E R C O I L O U T L E T
A N D A R E C E ! V E R I N L E T
F O R T H E T O T A L L O A D
W H E N R E C E ; V E R 1 S
V E N T E D T O C O I I . O U T L E T
H E A D E R ( B A S E D O N 1 0 '
O F H O R I Z O N T A L P I P E ,

1 V A L V E A N D 2 E L B O W S ) .

A P P L I E S T O 9 H T Y P E

E V A P . C O N D E N S E R

- R E F R I G . G A S

- R E F I G . L I Q U I D

Fig. 19 - Typical Refrigerant Piping 30HJ020-030 Units

with 9H Evaporative Condenser

15