Sequence of operation, 30hh,hj, Carrier – Carrier 30HH User Manual
Page 41: Installation
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Carrier
INSTALLATION
30HH,HJ
is the farthest to the right. The 30HH015 and
30HJ015 units are provided with two unloading
devices on its single compressor. Each unload
ing device is the cylinder head bypass type and
unloads
two
cylinders
when
the
operating
so
lenoid is energized. Cylinder unloaders are en
ergized
and
de-energized
by
the
cam
operated
load switches in the step controller.
Chilled Water Temperature Controller - The
chilled
water
temperature
controller
supplied
with each 30HH,HJ unit is the modulating re
mote bulb type with set point and throttling range
adjustments.
The
remote
bulb,
field-inserted
in
the chilled water line, relays the chilled water
temperature
signal
to
the
temperature
controller
potentiometer
which
actuates
the
step
controller.
To use the factory cam settings on the step con
troller, the remote bulb of the temperature con
troller
must
be
inserted
in
the
return
chilled
water line.
Control Bulb Location - It is generally required
with all liquid chilling package applications that
the
leaving
chilled
water
temperature
be
con
trolled. On liquid chilling packages where capac
ity can be controlled by a throttling device, the
leaving
chilled
water
temperature
is
usually
controlled
by
placing
the
temperature
control
bulb in the leaving chilled water line. However,
with
any
reciprocating
liquid
chilling
package,
where capacity is controlled by cylinder unload
ing
or
stopping
and
starting
compressors,
the
reliability and accuracy of control of the leaving
chilled
water
temperature
are
inherently
better
with the control bulb located in the return (en
tering) chilled water line. For this reason, the
factory settings of the step controller cams on
all 30HH,HJ units are based on control from the
return
(entering)
chilled
water
temperature.
If
the unit is to be applied with the control bulb in
the leaving chilled water line, the cams must be
reset in the field. If this is required, contact
the local Minneapolis-Honeywell representative.
The use of return chilled water control and fac
tory cam settings on the step controller apply
to
systems
designed
for
constant
chilled
water
gpm thru the cooler.
SEQUENCE OF OPERATION
The sequence of control operation of the 30HH,HJ
packages may be followed by referring to the
control circuit diagram on the following page.
With power to the control circuit and the "OFF-
ON” switch in the "OFF" position, the com
pressor
crankcase
heaters
are
energized.
When
the "OFF-ON" switch is put in the "ON" posi
tion, the panel light goes on and, with the chilled
water
safety
thermostat
and
the
field-supplied
auxiliary
interlocks
satisfied,
the
low
voltage
transformer
is
energized.
The
recycle
relay
energizes
the
camshaft
drive
motor
thru
the
balancing relay so that the camshaft is recycled
to the no load position. When the unload direc
tion
limit
is
reached,
the
recycle
relay
puts
power to the cam operated load switches and the
temperature
controller
takes
control.
By
recy
cling the controls at start-up or after a power
interruption, staggered starting of multiple com
pressors is insured.
With
the
temperature
controller
in
control
the
position
of
the camshaft is
regulated according
to the chilled water temperature. The cam oper
ated
load
switches
start
or
stop
compressors
and alternately load and unload cylinders of one
compressor to control the capacity of the unit
and balance it with the required load. During
operation a change in temperature causes an un
balance
in
the
temperature
bridge
circuit.
This
causes the balancing relay to energize the cam
shaft drive motor winding which turns the cam
shaft to increase or decrease the unit capacity
as required.
All 30HH and HJ units are designed with Liquid
Line Solenoid Drop. The liquid line solenoid in
each refrigerant circuit is in parallel with the
holding coil for the compressor in that circuit.
The solenoid is energized when the compressor
starts and the liquid line valve opens. When the
compressor
stops,
the
solenoid
is
de-energized
and the valve closes. Where a refrigerant circuit
has more than one compressor, the liquid line
valve
opens
when
the
first
compressor
starts
and closes when the last compressor stops.
The complete unit is stopped if the "OFF-ON"
switch is put in the "OFF" position; if the chilled
water safety thermostat contacts open; or if the
contacts
of
any
auxiliary
interlock
open.
Indi
vidual
compressors
are
stopped
if
the
motor
winding
high
temperature
cutout
contacts
open
or if the high or low pressure switch of the re
frigerant circuit cuts out.
The
compressor
crankcase
heater
is
turned
on
when the compressor is cycled off to prevent
dilution and crankcase refrigerant condensation.
35