beautypg.com

Sequence of operation, 30hh,hj, Carrier – Carrier 30HH User Manual

Page 41: Installation

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Carrier

INSTALLATION

30HH,HJ

is the farthest to the right. The 30HH015 and
30HJ015 units are provided with two unloading

devices on its single compressor. Each unload­
ing device is the cylinder head bypass type and
unloads

two

cylinders

when

the

operating

so­

lenoid is energized. Cylinder unloaders are en­
ergized

and

de-energized

by

the

cam

operated

load switches in the step controller.

Chilled Water Temperature Controller - The
chilled

water

temperature

controller

supplied

with each 30HH,HJ unit is the modulating re­
mote bulb type with set point and throttling range
adjustments.

The

remote

bulb,

field-inserted

in

the chilled water line, relays the chilled water
temperature

signal

to

the

temperature

controller

potentiometer

which

actuates

the

step

controller.

To use the factory cam settings on the step con­

troller, the remote bulb of the temperature con­
troller

must

be

inserted

in

the

return

chilled

water line.

Control Bulb Location - It is generally required
with all liquid chilling package applications that
the

leaving

chilled

water

temperature

be

con­

trolled. On liquid chilling packages where capac­
ity can be controlled by a throttling device, the
leaving

chilled

water

temperature

is

usually

controlled

by

placing

the

temperature

control

bulb in the leaving chilled water line. However,
with

any

reciprocating

liquid

chilling

package,

where capacity is controlled by cylinder unload­
ing

or

stopping

and

starting

compressors,

the

reliability and accuracy of control of the leaving
chilled

water

temperature

are

inherently

better

with the control bulb located in the return (en­
tering) chilled water line. For this reason, the
factory settings of the step controller cams on

all 30HH,HJ units are based on control from the
return

(entering)

chilled

water

temperature.

If

the unit is to be applied with the control bulb in
the leaving chilled water line, the cams must be
reset in the field. If this is required, contact
the local Minneapolis-Honeywell representative.

The use of return chilled water control and fac­
tory cam settings on the step controller apply
to

systems

designed

for

constant

chilled

water

gpm thru the cooler.

SEQUENCE OF OPERATION

The sequence of control operation of the 30HH,HJ

packages may be followed by referring to the

control circuit diagram on the following page.

With power to the control circuit and the "OFF-

ON” switch in the "OFF" position, the com­
pressor

crankcase

heaters

are

energized.

When

the "OFF-ON" switch is put in the "ON" posi­
tion, the panel light goes on and, with the chilled
water

safety

thermostat

and

the

field-supplied

auxiliary

interlocks

satisfied,

the

low

voltage

transformer

is

energized.

The

recycle

relay

energizes

the

camshaft

drive

motor

thru

the

balancing relay so that the camshaft is recycled

to the no load position. When the unload direc­
tion

limit

is

reached,

the

recycle

relay

puts

power to the cam operated load switches and the

temperature

controller

takes

control.

By

recy­

cling the controls at start-up or after a power
interruption, staggered starting of multiple com­

pressors is insured.

With

the

temperature

controller

in

control

the

position

of

the camshaft is

regulated according

to the chilled water temperature. The cam oper­
ated

load

switches

start

or

stop

compressors

and alternately load and unload cylinders of one
compressor to control the capacity of the unit
and balance it with the required load. During

operation a change in temperature causes an un­

balance

in

the

temperature

bridge

circuit.

This

causes the balancing relay to energize the cam­
shaft drive motor winding which turns the cam­
shaft to increase or decrease the unit capacity
as required.

All 30HH and HJ units are designed with Liquid
Line Solenoid Drop. The liquid line solenoid in
each refrigerant circuit is in parallel with the
holding coil for the compressor in that circuit.
The solenoid is energized when the compressor
starts and the liquid line valve opens. When the
compressor

stops,

the

solenoid

is

de-energized

and the valve closes. Where a refrigerant circuit

has more than one compressor, the liquid line
valve

opens

when

the

first

compressor

starts

and closes when the last compressor stops.

The complete unit is stopped if the "OFF-ON"

switch is put in the "OFF" position; if the chilled

water safety thermostat contacts open; or if the
contacts

of

any

auxiliary

interlock

open.

Indi­

vidual

compressors

are

stopped

if

the

motor

winding

high

temperature

cutout

contacts

open

or if the high or low pressure switch of the re­

frigerant circuit cuts out.

The

compressor

crankcase

heater

is

turned

on

when the compressor is cycled off to prevent
dilution and crankcase refrigerant condensation.

35