2 mounting the evs-50w, 2 mounting the evs-50w -14 – SilentKnight EVS User Manual
Page 36
EVS Series Emergency Voice System Installation Manual
4-14
LS10062-001-SK-E
4.5.2
Mounting the EVS-50W
The EVS-50W is equipped with a separate enclosure. Refer to Section 4.1 when
selecting a mounting location for the EVS-50W.
The panel should be accessible to main drop wiring runs. It should be mounted as
close to the center of the building as possible and located within a secured area, but
should be accessible for testing and service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When
mounting on concrete, especially when moisture is expected, attach a piece of 3/4-
inch plywood to the concrete surface and then attach the cabinet to the plywood. Also
mount any other modules to the plywood.
The cabinet can be surface or flush-mounted. If you will be flush-mounting the
cabinet, the hole for the enclosure should be 14½” W x 24¾” H x 3-7/16” D (36.8cm
W x 62.9cm H x 8.73cm D). Do not flush-mount in a wall designated as a fire break.
The Outside dimensions of the cabinet are 16" W x 26 ¼” H x 4-1/8” D (40.64cm W x
66.68cm H x 10.48cm D).
Follow these steps to properly mount the cabinet.
1. On the mounting surface install two screws level with each other 11" apart.
Figure 4-15 Cabinet Flush Mount Dimensions and Mounting Hole Locations
2. Install the cabinet onto the two mounting screws and tighten the screws.
3. Insert two screws into the two bottom mounting holes.
Key Holes
Bottom Mounting
Holes