beautypg.com

2 underwriters laboratories (ul), 1 requirements for all installations, Underwriters laboratories (ul) -2 – SilentKnight EVS User Manual

Page 16

background image

EVS Series Emergency Voice System Installation Manual

2-2

LS10062-001-SK-E

2.2 Underwriters Laboratories (UL)

2.2.1

Requirements for All Installations

General requirements are described in this section. When installing an individual
device, refer to the specific section of the manual for additional requirements. The
following subsections list specific requirements for each type of installation (for
example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems,
and so on).

1. All field wiring must be installed in accordance with NFPA 70 National Electric

Code.

2. Use the addressable smoke detectors specified in FACP installation manual.

3. Use UL listed notification appliances compatible with the FACP from those speci-

fied in the Appendix at the back of this manual.

4. UL installations using Class B wiring for the speaker circuit require the use of an

EOL resistor assembly.

5. A full system checkout must be performed any time the panel is programmed.

2.2.2

Requirements for Central Station Fire Alarm
Systems

1. Use both phone lines. Enable phone line monitors for both lines.

2. You must program a phone number and a test time so that the FACP sends an

automatic daily test to the central station.

3. Do not use the ground start option.

4. The AC Loss Hours option must be set from 1-3 hours.

5. The Attempts to Report option must be set for 5.

2.2.3

Requirements for Local Protected Fire Alarm
Systems

At least one UL listed supervised notification appliance must be used.