This section contains information necessary to install the 5104 Fire Communicator and accessories.

3.1

Electrical Specifications

3.2

Environmental Specifications

It is important to protect the 5104 panel from water. To prevent water damage, the following precautions should
be FOLLOWED when mounting the unit:

Mount indoors in dry locations only

Do not mount directly on exterior walls, especially masonry walls (condensation).

Do not mount directly on exterior walls below grade (condensation).

Protect from plumbing leaks.

Protect from splash caused by sprinkler system inspection ports.

Do not mount in areas with humidity-generating equipment (such as dryers, production machinery, etc.).

Operating temperature range is 32° to 120° F (0° to 49° C).

Indoor use only.

10% to 93% non-condensing humidity at 30°C (86°F).

Non-corrosive environment.

Primary AC

120 Vrms @ 60Hz, 374 ma

Total DC load

1.3 Amp

Accessory Power

12 VDC @ 750 mA

Phone Line Voltage

2.75 VDC min.

Smoke Power

12 VDC @ 750 mA

Battery Charging Voltage

13.8 VDC

Minimum Low Battery Detection

10.2 VDC

Minimum Low AC Detection

102 Vrms @ 60 Hz, full load

Auxiliary Notification Appliance Circuit

12 VDC @ 500 mA