SilentKnight 5104 Digital Alarm Communicator Transmitter 6 Zone User Manual
Page 44
Model 5104B Installation Manual
151053-L8
8-2
Bell Trouble
Trouble condition on the notification
circuit.
Over current draw on the notification
circuit. Missing or incorrect EOL on a
supervised notification circuit.
L6 Flashes
Trouble Com 1
Event reports, auto test or manual
test unable to report on line 1.
Phone line voltage is O.K. but the
panel was unable to communicate on
line 1. Try dialing the phone number
that you programmed, from a
premise phone, to verify it is reaching
the central station. If that checks out
O.K. verify that you are using a
compatible reporting format with that
receiver.
L7 Flashes
Trouble Com 2
Event reports, auto test or manual
test unable to report on line 2.
Phone line voltage is O.K. but the
panel was unable to communicate on
line 2. Try dialing the phone number
that you programmed, from a
premise phone, to verify it is reaching
the central station. If that checks out
O.K. verify that you are using a
compatible reporting format with that
receiver.
Supervisory # (1-6)
Alarm condition on the zone
programmed as the sprinkler zone.
Short on the programmed sprinkler
zone.
Low Battery
Backup battery voltage is below 10.2
VDC.
Check backup battery connection.
Check backup battery voltage level
with volt meter. Replace the backup
battery.
L1 On
Blank
+12 Accessory power fault
Check for over current on terminal
24.
LED
Indications
5230 LCD Messages
Meaning
Cause and Correction