SilentKnight 5104 Digital Alarm Communicator Transmitter 6 Zone User Manual

Page 44

background image

Model 5104B Installation Manual

151053-L8

8-2

Bell Trouble

Trouble condition on the notification
circuit.

Over current draw on the notification
circuit. Missing or incorrect EOL on a
supervised notification circuit.

L6 Flashes

Trouble Com 1

Event reports, auto test or manual
test unable to report on line 1.

Phone line voltage is O.K. but the
panel was unable to communicate on
line 1. Try dialing the phone number
that you programmed, from a
premise phone, to verify it is reaching
the central station. If that checks out
O.K. verify that you are using a
compatible reporting format with that
receiver.

L7 Flashes

Trouble Com 2

Event reports, auto test or manual
test unable to report on line 2.

Phone line voltage is O.K. but the
panel was unable to communicate on
line 2. Try dialing the phone number
that you programmed, from a
premise phone, to verify it is reaching
the central station. If that checks out
O.K. verify that you are using a
compatible reporting format with that
receiver.

Supervisory # (1-6)

Alarm condition on the zone
programmed as the sprinkler zone.

Short on the programmed sprinkler
zone.

Low Battery

Backup battery voltage is below 10.2
VDC.

Check backup battery connection.
Check backup battery voltage level
with volt meter. Replace the backup
battery.

L1 On

Blank

+12 Accessory power fault

Check for over current on terminal
24.

LED

Indications

5230 LCD Messages

Meaning

Cause and Correction