Model 5104B Installation Manual

151053-L8

6-8

Step 37

Computer CIC

1 to 8-digits

None

Carrier Identification Code is the prefix that
needs to be dialed before a phone number to
access a particular long distance carrier. Use
special characters to add pauses, #, *, and
“look for second dial tone” characters into the
phone number. See Table 6-2 for special
characters.

Step 38

Computer Phone

1 to 16-digits

None

Enter up to 16 digits for phone number 1. Use
special characters to add pauses, #, *, and
“look for second dial tone” characters into the
phone number. See Table 6-2 for special
characters.

Step 39

Zone Response #1

0 = 0.3 to 0.4 sec.

1 = 3 to 4 sec.

2 = 16 to 20 sec.

3 = 32 to 40 sec.

1

Select the speed that this zone will respond to
alarm, trouble, or restore conditions. Selection
0 is not recommended, as it may cause
unnecessary alarm. Selection 2 & 3 are
considered delayed response. Delayed
responses may be used only on waterflow
switches, unless the waterflow switch has a
built-in delay. Any selection other than 0 - 3 will
scroll through the available selections.

Step 40

Zone Response #2

1

See Step 39

Step 41

Zone Response #3

1

Step 42

Zone Response #4

1

Step 43

Zone Response #5

1

Step 44

Zone Response #6

1

Step 45

Installers Code

4-digits

5104

Enter a 4-digit code to be used by the installer
or service technician.

The installer code allows the user to initiate
downloads, set time, and entering program
mode.

Step 46

Operators Code

4-digits

1111

Enter a 4-digit code to be used by the operator.

The operator code allows the user to silence
annunciations and to conduct manual tests.

Step 47

Test Time

24-hrs military

time

01:30

Enter the time that a automatic test will be sent
to central station. Use a 24-hour military time
format. For example, to enter the time 5:15 pm
enter 17:15. Use leading zeros for single-digit
hours, such as 01:30 etc.

Note:

Any events that have not been re-

stored will be sent along with the test report.

Step 48

Test Interval

0-3

3

Enter how often the control panel will do an
automatic phone test, keyed off the Test Time.
Selections 0-3 respectively; every 4 hours, 6
hours, 12 hours or 24 hours.

Table 6-3: List of Programming Steps

Step #

Task

Choices

Default