Model 5104B Installation Manual
151053-L8
6-8
Step 37
Computer CIC
1 to 8-digits
None
Carrier Identification Code is the prefix that
needs to be dialed before a phone number to
access a particular long distance carrier. Use
special characters to add pauses, #, *, and
“look for second dial tone” characters into the
phone number. See Table 6-2 for special
characters.
Step 38
Computer Phone
1 to 16-digits
None
Enter up to 16 digits for phone number 1. Use
special characters to add pauses, #, *, and
“look for second dial tone” characters into the
phone number. See Table 6-2 for special
characters.
Step 39
Zone Response #1
0 = 0.3 to 0.4 sec.
1 = 3 to 4 sec.
2 = 16 to 20 sec.
3 = 32 to 40 sec.
1
Select the speed that this zone will respond to
alarm, trouble, or restore conditions. Selection
0 is not recommended, as it may cause
unnecessary alarm. Selection 2 & 3 are
considered delayed response. Delayed
responses may be used only on waterflow
switches, unless the waterflow switch has a
built-in delay. Any selection other than 0 - 3 will
scroll through the available selections.
Step 40
Zone Response #2
1
See Step 39
Step 41
Zone Response #3
1
Step 42
Zone Response #4
1
Step 43
Zone Response #5
1
Step 44
Zone Response #6
1
Step 45
Installers Code
4-digits
5104
Enter a 4-digit code to be used by the installer
or service technician.
The installer code allows the user to initiate
downloads, set time, and entering program
mode.
Step 46
Operators Code
4-digits
1111
Enter a 4-digit code to be used by the operator.
The operator code allows the user to silence
annunciations and to conduct manual tests.
Step 47
Test Time
24-hrs military
time
01:30
Enter the time that a automatic test will be sent
to central station. Use a 24-hour military time
format. For example, to enter the time 5:15 pm
enter 17:15. Use leading zeros for single-digit
hours, such as 01:30 etc.
Note:
Any events that have not been re-
stored will be sent along with the test report.
Step 48
Test Interval
0-3
3
Enter how often the control panel will do an
automatic phone test, keyed off the Test Time.
Selections 0-3 respectively; every 4 hours, 6
hours, 12 hours or 24 hours.
Table 6-3: List of Programming Steps
Step #
Task
Choices
Default