beautypg.com

8 ac connection, 1 standard transformer connections, 9 battery connection – SilentKnight 5104 Digital Alarm Communicator Transmitter 6 Zone User Manual

Page 18: Ac connection -10, 1 standard transformer connections -10, Battery connection -10

background image

Model 5104B Installation Manual

151053-L8

3-10

3.8

AC Connection

3.8.1

Standard Transformer Connections

The AC transformer is factory mounted into the control panel and is plugged onto the control panel as shown in
Figure 3-4. The ground and the primary side of the transformer should be wired as shown in Figure 3-4 by a
certified electrician.

Figure 3-4 AC Transformer Connections

3.9

Battery Connection

The battery provides backup power to the system during AC power loss. Connect the 12 VDC battery (SK Model
6712) as shown in Figure 3-5.

Figure 3-5 Backup Battery Connections

Note: Observe proper polarity when connecting the 12 VDC battery to 5104. If polarity is reversed, a resettable

overcurrent protection device on the 5104 will automatically open removing power from the panel.

Green
Ground Wire

Red
Transformer Wires

AC Plug

Replace battery
Every 5 years