beautypg.com

2 supervised notification appliance wiring, 2 supervised notification appliance wiring -16 – SilentKnight 5104 Digital Alarm Communicator Transmitter 6 Zone User Manual

Page 23

background image

Installation

151053-L8

3-15

3.11.2 Supervised Notification Appliance Wiring

When using a supervised notification device any open or shorted wiring condition will be reported as a trouble.
Figure 3-10 illustrates how to wire a supervised notification device to the control panel. Refer to Section 6.2.7
Step 14 to program the notification circuit’s supervision properties.

Figure 3-10 Supervised Alarm Bell Wiring

Note: Polarities shown in Figure 3-10 illustrate the polarity in an alarm condition. Under normal conditions the

polarity of terminals 21 and 22 are reversed.

Model 7628

4.7 K

EOL

Wheelock

Model MB-G10-12-R

12 VDC Bell