Model 5104B Installation Manual

151053-L8

6-6

Step 21

Report Sprnk #3

Yes or No

No

Set how zone 3 will report. Press any numeric-
digit to toggle the selection from Yes to No.

Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.

No = If you want troubles and alarms to report
as fires (Alarm).

Note:

Bells will only sound if “No” is select-

ed.

Step 22

Report Sprnk #4

Yes or No

No

Set how zone 4 will report. Press any numeric-
digit to toggle the selection from Yes to No.

Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.

No = If you want troubles and alarms to report
as fires (Alarm).

Note:

Bells will only sound if “No” is select-

ed.

Step 23

Report Sprnk #5

Yes or No

No

Set how zone 5 will report. Press any numeric-
digit to toggle the selection from Yes to No.

Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.

No = If you want troubles and alarms to report
as fires (Alarm).

Note:

Bells will only sound if “No” is select-

ed.

Step 24

Report Sprnk #6

Yes or No

No

Set how zone 6 will report. Press any numeric-
digit to toggle the selection from Yes to No.

Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.

No = If you want troubles and alarms to report
as fires (Alarm).

Note:

Bells will only sound if “No” is select-

ed.

Step 25

Latch Sprnk

Yes or No

No

Set how the sprinkler zone will operate. Press
any numeric-digit to toggle the selection from
Yes to No.

Yes = When the sprinkler zone shorts for a
duration longer than the Zone Response (set in
steps 39 through 44), the annunciator remains
active until reported or manually silenced.

No = When the sprinkler zone shorts for a
duration longer than the Zone Response (set in
steps 39 through 44), the zone will follow
system status and indicate a supervisory on
that zone for the duration of the faulted
condition.

Table 6-3: List of Programming Steps

Step #

Task

Choices

Default