Section 5 5230 operation, 1 5230 display messages, 5230 display messages -1 – SilentKnight 5104 Digital Alarm Communicator Transmitter 6 Zone User Manual
Page 28

151053-L8
5-1
Section 5
5230 Operation
This section contains information about the operation of the 5104 through a 5230 remote annunciator.
5.1
5230 Display Messages
If the 5104 is not reporting, being programmed, and if no functions are being entered, the LCD will
display the event of the highest priority. For example if a supervisory and an alarm condition has
occurred, the alarm condition will be displayed on the top line of the annunciator and any other low
priority events will be displayed on the lower line of the annunciator in abbreviated form. (See Figure 5-
1.)
Figure 5-1 Example of Displayed Messages
Table 5-1 lists of the 5230 messages:
Table 5-1: 5230 LCD Messages and Meanings
Message
Meaning
Trouble Zone # (1-6)
Trouble condition exist on the zone or zones indicated by #
Alarm Zone # (1-6)
Alarm condition exist on the zone or zones indicated by #
Low AC
AC power has been lost.
Trouble Line 1
Trouble condition on phone line 1.
Trouble Line 2
Trouble condition on phone line 2.
Dialer Trouble
Indicates a dialer failed condition.
Earth Ground Fault
Indicates that an earth ground fault condition exists.
Earth Pwr Fault
Indicates that an earth ground to power, fault condition exists.
Silenced
A trouble condition exists and the annunciation has been turned off.
System Normal
Displayed if no trouble, alarm or 5230 system error exists.
Data Lost
Displayed if event memory overflows.
Reporting
A report is being transmitted to central station.
Up/Download
Data is being uploaded or downloaded from the central station computer.
Bus Trouble
The 5230 cannot communicate with 5104.
Try Again
If there is a 10 seconds time lapse between key presses while entering a function,
the 5230 will display this message. An invalid entry was made.
Supervisory
Condition Only
Alarm High
Priority Event
Indicates Other Event Have Occurred