Table 7-2: Event and Reporting Code by Format
Event
SIA8 &
20
SK4/2
3/1 1400 &2300
BFSK14 & 23
Contact ID
Fire Alarm 1-6
FA1 -
FA6
01 - 06
Alarm Code
01 - 06
1 110 001 - 1
110 006
Fire Alarm Restore 1-6
FH1 -
FH6
21 - 26
Restore Code
E1 - E6
3 110 001 - 3
110 006
Fire Trouble 1-6
FT1 -
FT6
61 - 66
Trouble Code
F1 - F6
1 373 001 - 1
373 006
Fire Trouble Restore 1-6
FJ1 - FJ6
71 - 76
Restore Code
E1 - E6
3 373 001 - 3
373 006
Sprinkler Supervisory 1-6
SS1 -
SS6
01 -06
Sprinkler Code
01 - 06
1 203 001 - 1
203 006
Sprinkler Supervisory Restore 1-6
SR1 -
SR6
21 - 26
Restore Code
E1 - E6
3 203 001 - 3
203 006
Sprinkler Trouble 1-6
ST1 -
ST6
61 - 66
Trouble Code
F1 - F6
1 203 001 - 1
203 006
Sprinkler Trouble Restore 1-6
SJ1 - SJ6
71 - 76
Restore Code
E1 - E6
3 203 001 - 3
203 006
Annunciator Trouble 1-3
ET1 -
ET3
33
Trouble Code
FD
1 330 001 - 1
330 003
Annunciator Restore 1-3
ER1 -
ER3
37
Restore Code
ED
3 330 001 - 3
330 003
Bell Trouble
ET32
33
Trouble Code
FD
1 320 001
Bell Restore
ER32
37
Restore Code
ED
3 320 001
Earth Ground Trouble
ET38
33
Trouble Code
FD
1 310 000
Earth Ground Restore
ER38
37
Restore Code
ED
3 310 000
Earth Power Trouble
ET39
33
Trouble Code
FD
1 310 000
Earth Power Restore
ER39
37
Restore Code
ED
3 310 000
Smoke (Loop) Power Trouble
ET40
33
Trouble Code
FD
1 300 000
Smoke (Loop) Power Restore
ER40
37
Restore Code
ED
3 300 000
Aux Power Trouble
ET43
33
Trouble Code
FD
1 300 003
Aux Power Restore
ER43
37
Restore Code
ED
3 300 003
AC Trouble
AT0
60
Trouble Code
FA
1 301 000
AC Restore
AR0
70
Restore Code
EA
3 301 000
Battery Trouble
YT0
69
Trouble Code
F9
1 302 000
Battery Restore
YR0
79
Restore Code
E9
3 302 000