3.5.2

Current Draw Worksheet

Use this worksheet to determine current requirements during alarm/battery standby operation.

Table 3-6: Current Draw Calculations

Device

Number of

Devices

Current per Device

Standby

Current

Alarm

Current

For each device use this
formula:

This Column

x

This Column

=

Current per number of

devices

5104

1

Standby: 75 mA

75 mA

Alarm: 135 mA

135 mA

5230

3 max

Standby: 25 mA

mA

Alarm: 40 mA

mA

A

Current Subtotals:

mA

mA

Smoke Detectors

Standby: mA

mA

Alarm: mA

mA

Standby: mA

mA

Alarm: mA

mA

Standby: mA

mA

Alarm: mA

mA

Standby: mA

mA

Alarm: mA

mA

Standby: mA

mA

Alarm: mA

mA

Standby: mA

mA

Alarm: mA

mA

B

Current Subtotals:

mA

mA

Notification Appliances

mA

mA

mA

mA

mA

C

Current Subtotals:

mA

D Total current rating of all devices in system (add totals of A-C) x .001:

A

A

E Number of standby hours. (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):

H

F Multiply lines D (standby current) and E.

Total standby AH

AH

G Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)

H

H Multiply lines D (alarm Current) and G totals

Total alarm AH

AH

I Add lines F and H. AH = Ampere Hours

Total AH required

AH