Programming

151053-L8

6-9

*

For UL certified systems Low AC Hours in Step 5 must be set from 1 - 3 hours.

Step 49

Add-on Dialer

Yes or No

No

Press any numeric-digit to toggle the selection
from Yes to No.

Yes = If the 5104 is used as an add-on
communicator for a host panel. This tells the
5104 not to test the battery or earth ground,
which could cause interference with the host
panel.

No = The 5104 will test battery and earth
ground.

see Table 6-1

Table 6-3: List of Programming Steps

Step #

Task

Choices

Default