4.0 Clearances

and

Dimensions

4.1 Clearances

FIGURE 2 -

Installing

High Altitude

Pressure Switch

required above

6000 ft (1830M)

elevation

Instructions for Changing Pressure Switch

1. In the control compartment, locate the pressure switch.

2. Mark and disconnect the two wires attached to the pressure switch.

3. Disconnect the sensing tubes from the pressure switch.

4. Locate the two screws holding the switch mounting bracket. Remove the screws and

the pressure switch. Save the screws.

5. Using the same screws, install the high altitude pressure switch. Attach the sensing

tubes and wires.

Pressure

Switch

Model UDBP
Size

30

45

60

75

100

125

150 175 200 225 250 300

350

400

High Altitude Switch P/N

197031

197032

197031

201160

Negative Pressure OFF

Setpoint ("w.c.)

0.35

0.45

0.35

1.05

Label color

Purple

Pink

Purple

Brown

Model UDBS
Size

30

45

60

75

100

125

150 175 200 225 250 300

350

400

High Altitude Switch P/N 197031 197032 196362 197032 197031 197030 197031

201160

Differential Pressure

OFF Setpoint ("w.c.)

0.35

0.45

0.55

0.45

0.35

0.40

0.35

1.05

Label color

Purple

Pink

White

Pink

Purple Green

Purple

Brown

Downturn Nozzle Kits,

Option CD 2, 3, 4, or 5

Follow the instructions with the kit to install. Additional length beyond the front of the

unit is shown in

FIGURE 3.

FIGURE 3 - With Optional Downturn Nozzle, Dimension “A”

3.0 Uncrating and

Preparation

(cont’d)

3.2 Preparing for Installation (cont’d)

A

A

With 25-65°

downturn

with or

without

vertical

louvers

(Option

CD2 or CD4)

With 50-90°

downturn

with or

without

vertical

louvers

(Option

CD3 or CD5)

Dimension A

UDBP and

UDBS Sizes

Options CD2 & CD4

Options CD3 & CD5

inches

mm

inches

mm

30, 45

7-1/8

181

12-3/8

314

60, 75

8-5/8

219

15

381

100, 125

12-5/8

321

21-7/8

556

150, 175, 200

11-1/2

292

19-7/8

505

225, 250

14-1/2

368

25-1/8

638

300, 350, 400

18-1/2

470

32

813

Units must be installed so that the clearances in

FIGURE 4 are provided for com-

bustion air space, inspection and service, and for proper spacing from combustible

construction. Clearance to combustibles is defined as the minimum distance from the

heater to a surface or object that is necessary to ensure that a surface temperature of

90°F above the surrounding ambient temperature is not exceeded.

UDBP and UDBS

Sizes

30-125

150-400

inches

mm

inches

mm

Top*

6

152

14

356

Flue Connector

6

152

6

152

Access Panel

18

457

18

457

*Non-Access Side

24

610

24

610

Bottom

1

25

1

25

Rear

18

457

18

457

REZNOR

Top clearance is from top

of the heater cabinet.

Non access side

clearance is

from side of the

heater cabinet.

FIGURE 4 - Clearances

If the pressure switch needs to be changed, do that before the heater is operated; fol-

low the instructions in

FIGURE 2.