beautypg.com

2 combustion air - models udbp, 0 mechanical (cont’d), 1 gas piping and pressures (cont’d) – Reznor UDBS Unit Installation Manual User Manual

Page 16

background image

Form I-UDB, P/N 202658 R14, Page 16

Combustion Air

Requirements for a

Heater Located in

a Confined Space -

applies to Model UDBP

6.2 Combustion Air - Models UDBP

This heater must be supplied with the air that enters into the combustion process and is

then vented to the outdoors. Sufficient air must enter the equipment location to replace

that exhausted through the heater vent system. In the past, the infiltration of outside air

assumed in heat loss calculations (one air change per hour) was assumed to be suf-

ficient. However, current construction methods using more insulation, vapor barriers,

tighter fitting and gasketed doors and windows, weather-stripping, and/or mechanical

exhaust fans may now require the introduction of outside air through wall openings or

ducts.
The requirements for combustion and ventilation air depend upon whether the unit is

located in a confined or unconfined space. An “unconfined space” is defined as a space

whose volume is not less than 50 cubic feet per 1000 BTUH of the installed appliance.

Under ALL conditions, enough air must be provided to ensure there will not be a

negative pressure condition within the equipment room or space.

WARNING

Model UDBP power-vented unit heaters are designed to take

combustion air from the space in which the unit is installed and

are not designed for connection to outside combustion air intake

ducts. Connecting outside air ducts voids the warranty and could

cause hazardous operation. See Hazard Levels, page 2.

Do not install a unit in a confined space without providing wall openings leading to and

from the space. Provide openings near the floor and ceiling for ventilation and air for

combustion as shown in

FIGURE 11, depending on the combustion air source as noted

in Items 1, 2, and 3 below.
Add total BTUH of all appliances in the confined space and divide by figures below for

square inch free area size of each (top and bottom) opening.

(Note: For Model

UDBS, see

Venting Manual

for combustion air

requirements.)

6.0 Mechanical

(cont’d)

6.1 Gas Piping and Pressures (cont’d)

6.1.3 Derate by Valve Outlet Pressure Adjustment for High Altitude

Operation (cont’d)

High Altitude

Capacity Changes

(cont’d)

BTUH Inputs and Capacities by Altitude in the UNITED STATES for Model UDBP and Model UDBS (cont'd)

ALTITUDE

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Feet

Meters

Size 200

Size 225

Size 250

Size 300

0-2000

0-610

200000

166000

140000 225000

186750

157500 250000

207500

175000 300000

249000

210000

2001-3000 611-915 188000

156040

131600 211500

175545

148050 235000

195050

164500 282000

234060

197400

3001-4000 916-1220 184000

152720

128800 207000

171810

144900 230000

190900

161000 276000

229080

193200

4001-5000 1221-1525 180000

149400

126000 202500

168075

141750 225000

186750

157500 270000

224100

189000

5001-6000 1526-1830 176000

146080

123200 198000

164340

138600 220000

182600

154000 264000

219120

184800

6001-7000 1831-2135 172000

142760

120400 193500

160605

135450 215000

178450

150500 258000

214140

180600

7001-8000 2136-2440 168000

139440

117600 189000

156870

132300 210000

174300

147000 252000

209160

176400

8001-9000 2441-2745 164000

136120

114800 184500

153135

129150 205000

170150

143500 246000

204180

172200

9001-10000 2746-3045 160000

132800

112000 180000

149400

126000 200000

166000

140000 240000

199200

168000

Feet

Meters

Size 350

Size 400

0-2000

0-610

350000

290500

245000 400000

332000

280000

2001-3000 611-915 329000

273070

230300 376000

312080

263200

3001-4000 916-1220 322000

267260

225400 368000

305440

257600

4001-5000 1221-1525 315000

261450

220500 360000

298800

252000

5001-6000 1526-1830 308000

255640

215600 352000

292160

246400

6001-7000 1831-2135 301000

249830

210700 344000

285520

240800

7001-8000 2136-2440 294000

244020

205800 336000

278880

235200

8001-9000 2441-2745 287000

238210

200900 328000

272240

229600

9001-10000 2746-3045 280000

232400

196000 320000

265600

224000

BTUH Inputs and Capacities by Altitude in CANADA for Models UDBP and UDBS

ALTITUDE

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Feet

Meters

Size 30

Size 45

Size 60

Size 75

0-2000

0-610

30000

24600

30000 45000

37350

45000 60000

49800

42000 75000

62250

52500

2001-4500 611-1373 27000

22140

27000 40500

33615

40500 54000

44820

37800 67500

56025

47250

Feet

Meters

Size 100

Size 125

Size 150

Size 175

0-2000

0-610

105000

88200

73500 120000

100800

84000 150000

124500

105000 175000

145250

122500

2001-4500 611-1373 94500

79380

66150 108000

90720

75600 135000

113400

94500 157500

132300

110250

Feet

Meters

Size 200

Size 225

Size 250

Size 300

0-2000

0-610

200000

166000

140000 225000

186750

157500 250000

207500

175000 300000

249000

210000

2001-4500 611-1373 180000

151200

126000 202500

170100

141750 225000

189000

157500 270000

226800

189000

Feet

Meters

Size 350

Size 400

0-2000

0-610

350000

290500

245000 400000

332000

280000

2001-4500 611-1373 315000

264600

220500 360000

302400

252000

This manual is related to the following products: