Form I-UDB, P/N 202658 R14, Page 30

5) Steady Heat - Control inputs are continuously monitored to ensure limit and pres-

sure switches are closed, flame is established, and the thermostat call for heat remains.

When the thermostat call for heat is removed, the control de-energizes the gas valve

and begins post-purge and fan/blower off delay timing.
6) Post Purge - The venter motor output remains on for a 45-second post-purge period

after the thermostat is satisfied.
7) Fan/Blower Off Delay - The fan/blower motor is de-energized after a blower off

delay of 120 seconds:

Interrupted Thermostat Call for Heat - If the thermostat demand for heat is removed

before the flame is recognized, the control will run the venter motor for the post purge

period and de-energize all outputs.
If the thermostat demand for heat is removed after successful ignition, the control will

de-energize the gas valve, run the venter motor through post purge, and run the fan/

blower motor on heat speed for the selected delay off time.
Ignition Retry - If flame is not established on the first trial for ignition period, the control

de-energizes the gas valve and the venter motor remains energized for an inter-purge

period of 10 seconds. The spark and gas valve are then re-energized, and the control

initiates another trial for ignition.
If flame is not established on the second trial for ignition, the control de-energizes the

gas valve, energizes the fan/blower motor on heat speed, and venter motor remains

energized. The fan/blower motor is shut off after 120 seconds. When the fan/blower

motor de-energizes, the spark and gas valve are re-energized and the control initiates

another trial for ignition. (This blower delay is self-healing feature for an open auxiliary

limit switch).
If flame is not established on the third trial for ignition period, the control de-energizes

the gas valve, and the venter motor remains energized for an inter-purge period of 10

seconds. The control then re-energizes the gas valve and spark and initiates another

trial for ignition.
If flame is not established on the fourth trial for ignition (initial try plus 3 re-tries), the

control de-energizes the gas valve and goes into lockout. The control goes to one flash

on the green LED to indicate ignition failure lockout.
Limit Switch Operation - The limit switch is ignored unless a call for heat is present

(W energized). If the limit switch is open and a call for heat is present, the control de-

energizes the gas valve and turns the fan/blower motor on heat speed and runs the

venter motor. The control will be in soft lockout and flashing fault code “3” before return-

ing to normal operation.

When the switch re-closes or the call for heat is lost, the control runs the venter motor

through post purge and runs the blower/fan motor through the selected fan off delay.
Pressure Switch - If the pressure switch opens before the trial for ignition period, the

venter motor will run through the pressure switch recognition delay (2 seconds), the

gas valve will be de-energized, and the venter motor will run through the postpurge

time. The control will re-start the heat cycle at the pressure switch proving state if the

call for heat still exists.
Pressure switch opening for less than 2 seconds during the trial for ignition period shall

not interrupt the heat cycle. (Gas valve will de-energize while the pressure switch is

open.)
If the pressure switch opens after a successful ignition, the control will de-energize the

gas valve. If flame is lost before the end of the 2 second pressure switch recognition

delay, the control will respond to the loss of flame. If the pressure switch remains open

for 2 seconds and the flame remains, the control de-energizes the gas valve, the venter

motor runs through post-purge, and the fan/blower motor runs on heat speed through

the selected blower off delay. When the blower off delay is over, the fan/blower motor

is de-energized, and a heat cycle is begun if the call for heat still exists.

Abnormal Heat Cycle

Functions

8.0 Controls and

Operation

(cont’d)

8.3 Ignition System

(cont’d)

Normal Heat Cycle Operating Sequence (cont’d)