Form I-UDB, P/N 202658 R14, Page 25

FIGURE 18D - Typical Wiring Diagram for Model UDBP or Model UDBS, Sizes 150-400, Two Stage

AG2-AN2-CL22

UDBP & UDBS SERIES 150-400

WD# 186441 REV #2

VENTER

CONTACTOR COIL

SPARK GAP

GREEN LED

FIELD CONTROL WIRING

150'
250'
350'

75'
125'
175'

#18 GA. WIRE
#16 GA. WIRE
#14 GA. WIRE

TOTAL WIRE

LENGTH

DISTANCE FROM
UNIT TO CONTROL

MIN. RECOMMENDED

WIRE GUAGE

LED

OPTIONAL FIELD WIRING

FIELD WIRING

OPTIONAL FACTORY

FACTORY WIRING

DSI CONTROL

FAST FLASH

1 FLASH

2 FLASH

3 FLASH

4 FLASH

STEADY OFF

LED FLASH CODES

NORMAL OPERATION CALL FOR HEAT

IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES

PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS

LIMIT SWITCH OPEN

PRESSURE SWITCH IS CLOSED BEFORE VENTER IS ENERGIZED

INTERNAL CONTROL FAULT OR NO POWER

YELLOW LED

FLAME SENSED

STEADY ON

SLOW FLASH

WEAK FLAME

UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)

FAST FLASH

IND

BK

NEUTRAL

W

MOTOR

LED

OK

FLAME

G

Y

NEUTRAL

BK

W

LIMIT CONTROL

R

R

R

R

BR

FLAME

ELECTRODE

FLAME

GROUND

P1-8

P1-3

P1-6

P1-5

P1-7

P1-9

BK

W

P1-2

P1-4

BL

24V

115/208/230

Y

BK

BR

R

L1

NEUTRAL

NEUTRAL

L1

COM

SEC

SYSTEM TRANSFORMER

EAC/BLO

WIRING

OF VENTER ENERGIZED

V

O

LT

BK

AT

O OR A

TC

3.0 AMP

C

R

W

G

Y

R

Y

PR

P3-4

P3-3

P3-2

NORMAL OPERATION NO CALL FOR HEAT

STEADY ON

G

GRD
LUG

40 VA

CAPACITOR

(SEE NOTE #6)

BR

BR/W

SPARK

TRANSFORMER

P3-5

P3-1

W

FUSE

(UDBS ONLY)

R

DOOR INTERLOCK

BLOWER MOTOR

208-230/3/60

OR

L1

T1

R OR BK

BLOWER MOTOR

CONTACTOR CONTACTS

L3

T3

L2

T2

R OR W

R

PROTECTED

MOTOR

BLOWER

INTERNALLY

G

LINE/1/60

GRD

LO

W

TWO STAGE

GAS VALVE

HIGH

MV

GAS VALVE

TWO STAGE

O

HIGH

LO

W

STG

STG

C

BR

BL

O

STG

LO

C

STG

HONEYWELL

ALT.

HONEYWELL

W2

R

W1

TERMINAL STRIP

G

O

HI

HI

Y

Y

PRESSURE

SWITCH

Y

BR

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

C

ONTR

OL SWIT

CH

Y

(UDBS ONL

Y

)

2

3

Y

BK

6

5

BK

DISCONNECT SWITCH

CUSTOMER'S

NOTES
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT

2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL

HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR
LEAD WIRE, FLAME ROLLOUT AND LIMIT WIRING WHICH MUST BE 150° C.

4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.

5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT

VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
6. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON 115V MODELS
150-400 AND 208/230V MODELS 100-400.
7. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON MODELS 150 - 400.

WITH F

AN SWIT

CH (SEE NO

TE #8)

RC

W2

W1

R

(OPT CL22)

TWO STEG DIGIT

AL

THERMOST

AT

G

8. VERIFY JUMPER ON THERMOSTAT TERMINALS R TO RC.

OPERATING SEQUENCE
1. SET THERMOSTAT AT LOWEST SETTING, FAN SWITCH

2. TURN ON MANUAL GAS VALVE.

3. TURN ON POWER TO UNIT.

4. SET THERMOSTAT AT DESIRED SETTING.
5. LOW STAGE OF THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT LOW RATE.
7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE FAN
MOTOR IS ENERGIZED.

10. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND
MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT
(SEE LIGHTING INSTRUCTIONS).

9. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS FAN OPERATION.

8. HIGH STAGE OF THERMOSTAT CALLS FOR HEAT, FIRING UNIT AT FULL RATE.

AT "AUTO" POSITION.