3 troubleshooting, 0 maintenance and service (cont’d) – Reznor UDBS Unit Installation Manual User Manual

Page 40

background image

Form I-UDB, P/N 202658 R14, Page 40

10.3 Troubleshooting

Check the Lights on

the DSI Integrated

Control Module

(Circuit Board)

The integrated circuit board monitors the operation of the heater and includes two

LED signal lights that indicate normal operation and various abnormal conditions. If

the heater fails to operate properly, check this signal to determine the cause and/or

to eliminate certain causes. LED is visible through viewport on Model UDBS. Remove

access panel on Model UDBP. See operating sequence in Paragraph 9.
Do not attempt to repair the DSI integrated control module (circuit board); the only field

replaceable component is the fuse.

Control Status - Green LED Codes

Steady ON Normal Operation, No call for heat

Fast Flash .Normal Operation, Call for heat

1 Flash ......System Lockout, Failed to detect or sustain flame

2 Flashes ..Pressure Switch Did Not Close within 30 Seconds of Venter Motor

3 Flashes ..High Limit or Flame Rollout Switch Open

4 Flashes ....Pressure Switch is Closed Before Venter Motor is Energized

Steady OFF Blown fuse, No Power, or Defective Board
Flame Status - Yellow LED Codes

Steady ON ..Flame is sensed

Slow Flash ..Weak flame (current below 1.0 microamps ± 50%)

Fast Flash ...Undesired Flame (valve open and no call for heat)

IMPORTANT: When using a multimeter to troubleshoot the 24 volt circuit, place the

meter’s test leads into the 5 or 9 pin connectors located on the ignition control. Do not

remove connectors or terminals from the electrical components. Doing so can result

in misinterpreted readings due to the ignition control board’s fault mode monitoring

circuits.

DSI Integrated Control Module (Circuit

Board) Trial Troubleshooting Flowchart

Trial for Ignition

Call for Heat

Is there a

spark across gap at

ignitor?

Does gas

ignite?

Is there minimum

flame current at the

flame sensor?

Is there

minimum flame current

at the control

module?

Replace control

module.

Check connections to flame

sensor and/or moisture in the

burner assembly.

Is the flame

sensor corroded?

Clean flame

sensor.

Is the sensor

located in flame

correctly?

Replace flame

sesnsor.

Reposition

flame sensor.

Is gas

flowing?

Is the ignitor

position correct in the

gas flow?

Check gas pressure

and supply voltage.

If either are low,

correct and repeat

startup.

Reposition

spark ignitor.

Is there

24VAC at the gas

valve?

Is there 24VAC

from gas valve output on

control module to

chassis?

Check wiring and

connections to

gas valve.

Replace

ignition

control

module.

Replace gas

valve.

Is there

spark voltage at

control?

Check high

voltage wire

continuity.

Is there 24V P1-2

to power control?

Replace

control

module.

Check wiring

and/or 24VAC

transformer output.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

NO

YES

YES

NO

YES

NO

YES

NO

10.0 Maintenance and Service (cont’d)