6.0 Mechanical

6.1 Gas Piping and

Pressures

6.1.1 Gas Supply and Connections

WARNING

This appliance is equipped for a maximum gas supply pressure

of 1/2 psi, 3.5 kPa, or 14 inches water column. Supply pressure

greater than 1/2 psi requires installation of an additional lockup-

type service regulator external to the unit.

WARNING: PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve

from the gas supply line which is to be tested. Cap or plug the supply line.
Test Pressures Below 1/2 PSI: Before testing, close the manual valve on the

heater.

All piping must be in accordance with requirements outlined in the National Fuel Gas

Code ANSI/Z223.1a (latest edition) or CSA-B149.1 and B149.2 (See Paragraph 2).

Gas supply piping installation should conform with good practice and with local codes.

Support gas piping with pipe hangers, metal strapping, or other suitable material; do

not rely on the heater to support the gas pipe.
The heater is orificed for operation with natural gas having a heating value of 1000 (±

50) BTU per cubic ft or propane gas with a heating value of 2500 (± 100) BTU per cubic

ft. If the gas at the installation does not meet these specifications, consult the factory

for proper orificing.
Pipe joint compounds (pipe dope) shall be resistant to the action of liquefied petroleum

gas or any other chemical constituents of the gas being supplied.

Install a ground joint union and manual shutoff valve upstream of the unit control sys-

tem, as shown in

FIGURE 9. Installation of a trap with a minimum 3” (76mm) drip leg

is required.
The unit is equipped with a nipple that extends outside the cabinet. The gas connection

is either 1/2” or 3/4”.
Leak-test all connections by brushing on a leak-detecting solution.

FIGURE 8 - Swivel

Connectors to Suspend the

Heater from 1” Pipe, Option

CK10

If ordered with swivel connectors for 1” pipe, Option CK10, use field-supplied hardware

to attach the swivels at the suspension holes. Suspend with 1” pipe. See

FIGURE 8.

Be sure the threaded

swivel connectors are

locked to the hanger

bars as illustrated.

5.0 Hanging the

Heater (cont’d)

Swivel Hanger

Field-supplied

3/8” Hex Nut and

Lock Washer

3/8” Hex Nut

3/8 Lock Washer

®

WARNING

All components of a gas supply system must be leak tested prior to placing equipment in

service. NEVER TEST FOR LEAKS WITH AN OPEN FLAME. Failure to comply could result

in personal injury, property damage, or death.