Form I-UDB, P/N 202658 R14, Page 22

7.0 Electrical

Supply and

Wiring (cont’d)

FIGURE 18A - Typical Wiring Diagram for Model UDBP or Model UDBS

Sizes 30-125, Single Stage

AG1-AK1-CL1 OR CL22

WD# 185282 REV #2

UDBP & UDBS SERIES 30-125

VENTER

PRESSURE SWITCH

SPARK GAP

GREEN LED

NOTES
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT

2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL

HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR
LEAD WIRE AND LIMIT WIRING WHICH MUST BE 150° C.

4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.

5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT

VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.

LED

Y

Y

DSI CONTROL

FAST FLASH

1 FLASH

2 FLASH

3 FLASH

4 FLASH

STEADY OFF

LED FLASH CODES

NORMAL OPERATION CALL FOR HEAT

IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES

PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS

LIMIT SWITCH OPEN

PRESSURE SWITCH IS CLOSED BEFORE VENTER IS ENERGIZED

INTERNAL CONTROL FAULT OR NO POWER

YELLOW LED

FLAME SENSED

STEADY ON

SLOW FLASH

WEAK FLAME

UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)

FAST FLASH

IND

BK

NEUTRAL

W

MOTOR

LED

OK

FLAME

G

Y

NEUTRAL

W

LIMIT CONTROL

R

R

R

R

BR

FLAME

ELECTRODE

FLAME

GROUND

P1-8

P1-3

P1-6

P1-5

P1-7

P1-9

BK

W

GAS VALVE

BL

BR

P1-2

P1-4

BL

24V

115 V

OL

T

Y

BK

BR

R

L1

NEUTRAL

NEUTRAL

L1

COM

SEC

SYSTEM TRANSFORMER

EAC/BLO

W

OF VENTER ENERGIZED

A

TO OR A

TC

3.0 AMP

C

R

W

G

Y

R

W1

TERMINAL STRIP

R

Y

PR

P3-4

P3-3

P3-2

NORMAL OPERATION NO CALL FOR HEAT

STEADY ON

G

G

G

G

G

GRD

SCREW

115/1/60

40 VA

SPARK

TRANSFORMER

W2

G

P3-5

P3-1

Y

W

FUSE

(UDBS ONLY)

R

DOOR INTERLOCK

(UDBS ONL

Y

)

DISC

ONNECT SWIT

CH

BK

BK

6. THREE SPEED MOTOR CONNECTIONS ARE AS FOLLOWS:
MODELS 30 & 45 USE BLUE MOTOR LEAD, CAP BLACK AND RED.
MODELS 60 - 125 USE BLACK MOTOR LEAD, CAP BLUE AND RED

(MEDIUM)

CAPACITOR

(HIGH)

BR

(LOW)

BR

THREE SPEED

BLOWER MOTOR

(SEE NOTE #6)

R

BL

BK

BK

BROWN - BR

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BLACK - BK

WIRING CODE

FACTORY WIRING

FIELD WIRING

WIRE CONNECTOR

OPTIONAL FACTORY
WIRING

FIELD CONTROL WIRING

DISTANCE FROM
UNIT TO CONTROL

TOTAL WIRE

350'

150'

LENGTH

250'

MIN. RECOMMENDED

175'

75'
125'

#18 GA. WIRE
#16 GA. WIRE
#14 GA. WIRE

WIRE GUAGE

(OPT CL1) SINGLE ST

A

GE

THERMOST

A

T

WITH F

AN SWIT

CH (SET ANT

. A

T 0.6 AMPS)

R

W

G

WITH F

AN SWIT

CH (SEE NO

TES #8

THR

U #9)

(OPT CL22)

T

WO ST

A

GE DIGIT

AL

THERMOST

A

T

RC

R

R

W2

G

W1

W1

G

7. VERIFY JUMPER ON CL22 THERMOSTAT TERMINALS R TO RC.
8. FAN SWITCH OR LOW STAGE OF CL22 THERMOSTAT ENERGIZES THE BLOWER MOTOR.
9. HIGH STAGE OF CL22 THERMOSTAT INITIATES A CALL FOR HEAT.

OPERATING SEQUENCE
1. SET THERMOSTAT AT LOWEST SETTING; FAN SWITCH

2. TURN ON MANUAL GAS VALVE.

3. TURN ON POWER TO UNIT.
4. SET THERMOSTAT AT DESIRED SETTING.

6. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
7. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT FULL RATE.
8. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER
MOTOR IS ENERGIZED.

9. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND
MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT
(SEE LIGHTING INSTRUCTIONS).
10. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS BLOWER

AT "AUTO" POSITION.

OPERATION.

5. LOW STAGE OF THERMOSTAT ENERGIZES THE BLOWER
MOTOR FOR AIR RE-CIRCULATION.

7.4 Wiring Diagrams