beautypg.com

4 blowers, belts, and drives, 0 mechanical (cont’d), 3 unit discharge (cont’d) – Reznor UDBS Unit Installation Manual User Manual

Page 18: 1 belt 6.4.2 adjusting blower speed

background image

Form I-UDB, P/N 202658 R14, Page 18

6.3 Unit Discharge

(cont’d)

6.0 Mechanical

(cont’d)

Size CFM at 60°F

Temp Rise

Polytube

Diameter

(inches)

Approximate

Free Area

(square inches)

Suggested Hole Sizes and Locations by Length

Polytube

Holes

Length of Polytube

50 Ft

75 Ft 100 Ft 125 Ft 150 Ft

75*

960

18

115

Quantity

75 pairs 75 pairs 75 pairs 75 pairs 75 pairs

Diameter

1"

1"

1"

1"

1"

Spacing

8"

12"

16"

20"

24"

100*

1345

18

160

Quantity

48 pairs 48 pairs 48 pairs 48 pairs 48 pairs

Diameter

1-1/2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

Spacing

12-1/2" 18-3/4"

25"

31-1/4" 37-1/2"

125*

1540

18

185

Quantity

50 pairs 50 pairs 50 pairs 50 pairs 50 pairs

Diameter

1-1/2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

Spacing

12"

18"

24"

30"

36"

150

1920

24

230

Quantity

40 pairs 40 pairs 40 pairs 40 pairs 45 pairs

Diameter

2"

2"

2"

2"

1-7/8"

Spacing

15"

22-1/2"

30"

37-1/2"

40"

175

2240

24

270

Quantity

50 pairs 50 pairs 80 pairs 80 pairs 80 pairs

Diameter

1-7/8"

1-7/8"

1-1/2"

1-1/2"

1-1/2"

Spacing

12"

18"

15"

18-3/4" 22-1/2"

200

2560

24

300

Quantity

50 pairs 50 pairs 50 pairs 50 pairs 50 pairs

Diameter

2"

2"

2"

2"

2"

Spacing

12"

18"

24"

30"

36"

225

2880

24

340

Quantity

42 pairs 42 pairs 42 pairs 42 pairs 42 pairs

Diameter

2-1/4"

2-1/4"

2-1/4"

2-1/4"

2-1/4"

Spacing

14"

21"

28"

35"

42"

250

3200

24

380

Quantity

50 pairs 50 pairs 50 pairs 60 pairs 60 pairs

Diameter

2-1/4"

2-1/4"

2-1/4"

2"

2"

Spacing

12"

18"

24"

25"

30"

300

3840

24

460

Quantity

60 pairs 60 pairs 75 pairs 75 pairs 75 pairs

Diameter

2-1/4"

2-1/4"

2"

2"

2"

Spacing

10"

15"

16"

20"

24"

350

4480

24

540

Quantity

50 pairs 50 pairs 50 pairs 50 pairs 50 pairs

Diameter

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

Spacing

12"

18"

24"

30"

36"

400

5120

24

600

Quantity

60 pairs 60 pairs 75 pairs 75 pairs 75 pairs

Diameter

2-1/2"

2-1/2"

2-1/4"

2-1/4"

2-1/4"

Spacing

10"

15"

16"

20"

24"

6.4 Blowers, Belts,

and Drives

Blower Model

Sizes 30-125 are equipped with a direct drive motor. Blower Model

Sizes 150-400 have an adjustable belt drive.

Size 150-400 units are equipped with Power Twist Plus blower belts. These belts are

designed in link sections allowing for easy sizing and adjustment. The belt is sized

at the factory for the proper tension. If the belt needs adjustment, the recommended

method of adjusting the belt length is to count the number of links and remove one

link for every 24. (A link is made up of two joining sections of belt. For easier removal

of links, turn the belt inside out. But be sure to turn it back before installing.) The belt

tension should be checked after the first 24 hours of running at full load and at regular

maintenance inspections. Proper belt tension is important to the long life of the belt

and motor.
The blower speed may be adjusted to achieve the desired outlet temperature, as long

as the adjustment is within the temperature rise and the static pressure limits shown on

the heater rating plate.

Direct drive motors are factory set as indicated in the chart on

page 19.

Belt drive motors are factory set at the nominal temperature rise specified

for that unit.

6.4.1 Belt

6.4.2 Adjusting

Blower Speed

FIGURE 13 (cont’d) - Requirements for field-supplied Polytube Duct

This manual is related to the following products: