8.2 DDC Controls, Options D10 and D14

If the heater was ordered with Option D10 or D14, it is equipped with a Novar Minio

control module. The Novar control with its accompanying relays and power transformer

are mounted in the control compartment of the unit. See

FIGURE 19A. This control

offers a wide variety of input and output points that can be configured to meet a wide

range of building management applications. User-selectable input types are Thermis-

tor, 4-20 milliamp, 1-5 volts, or digital.

FIGURE 19A -

DDC Control with

Transformer and

Relays is Mounted on

a Specially Designed

Bracket in the Control

Compartment

Control

Option D10 includes the controller and the sensor to be field mounted at the

heater discharge.

Option D14 requires a field-supplied sensor that is compatible with

the control. For regulatory compliance specifications, and safety precautions, review

the control manufacturer’s installation instructions in the literature bag.
The recommended location for mounting the sensor is on the side of a field-installed

optional downturn nozzle. See

FIGURE 19B for an illustration of the sensor included

with Option D10 and dimensions for mounting it on the nozzle side.

Center the

1” (25mm)

sensor hole

vertically on

the nozzle

side.

2-1/4”

(57mm)

2-1/4”

(57mm)

(76mm)

9/16”

(14mm)

9/16”

(14mm)

Ø 1”

(25mm)

Nozzle flange

that connects

to the heater

outlet.

Ø (4) 1/8”

(3mm)

Before installing the

discharge nozzle, drill the

holes in the side panel as

illustrated.

Mount the sensor on the nozzle side.
Drill a 7/8” hole in the cabinet top above the controller and install the bushing supplied

with the unit for running the sensor wire. Sensor wire is field-supplied. Wire the sensor

to the controller as illustrated on the heater wiring diagram.

FIGURE 19B - Recommended Location

for Mounting the Sensor is on the Side

Panel of a Discharge Nozzle (Option CD

2, 3, or 4)