3 unit discharge, Figure 12 - duct flange dimensions udbp and udbs – Reznor UDBS Unit Installation Manual User Manual

Page 17

background image

Form I-UDB, P/N 202658 R14, Page 17

Confined Space:

A space whose volume is less than

50 cubic feet per 1000 BTUH of the

installed appliance input rating

FIGURE 11 - Definition

of Confined Space and

Required Openings for

Combustion Air

(3)

(3)

(1)

(1)

(2)

(2)

Confined

Space

1. Air from inside the building -- openings 1 square inch free area per 1000 BTUH.

Never less than 100 square inches of free area for each opening. See (1) in

FIGURE 11.

2. Air from outside through duct -- openings 1 square inch free area per 2000

BTUH. See (2) in

FIGURE 11.

3. Air direct from outside -- openings 1 square inch free area per 4000 BTUH. See

(3) in

FIGURE 11.

NOTE: For further details on supplying combustion air to a confined space, see the

National Fuel Gas Code ANSI Z223.1a (latest edition).

Depending on how the heater was ordered, it is shipped with either horizontal louvers

or a factory-installed duct flange (Option AX4).
Shipped-separate, field-installed discharge options include a duct flange, vertical lou-

vers in addition to the horizontal louvers, a choice of one or two downturn nozzle

sections available with and without vertical louvers; and a polytube adapter for green-

house or similar applications. Follow the instructions included with the field-installed

option package to attach the parts to the heater.
Dimensions of the field-installed downturn nozzles are shown in Paragraph 3.2.
If equipped with a duct flange or a polytube adapter, field-suppled metal or polytube

ductwork will need to be installed. Duct flange dimensions are shown in

FIGURE 12.

Polytube adapter dimensions and polytube requirements are shown in

FIGURE 13.

6.3 Unit Discharge

FIGURE 12 - Duct

Flange Dimensions

UDBP and

UDBS

"W"

"H"

inches

mm

inches

mm

30, 45

13-13/16

351

10

254

60, 75

13-13/16

351

13

330

100, 125

13-13/16

351

21

533

150, 175, 200

23

584

16

406

225, 250

23

584

22

559

300, 350, 400

23

584

30

762

3/4”

(19mm) typ

3/4” (19mm) typ

H

W

H and W are

the opening

dimensions.

Duct Flange

is 3/4” (19mm).

A

B

B

C

Polytube

Adapter

Option CD11

Model UDBP

or UDBS

Heater

Polytube

Ductwork

(field-supplied;

see table,

next page)

FIGURE 13 - Polytube Adapter Dimensions and Requirements for field-supplied Polytube

UDBP & UDBS

A

B

C

75

inches

16-15/16 10-3/8

9

mm

430

264

229

100, 125

inches

17

10-3/8

9

mm

432

264

229

150, 175,

200

inches

16-3/16 13-3/8 12

mm

411

340

305

225, 250

inches

16-3/16 13-3/8 12

mm

411

340

305

300, 350,

400

inches

16-3/16 13-3/8 12

mm

411

340

305