WARNINGS

Check the supporting structure to be used to verify that it has sufficient load carrying

capacity to support the weight of the unit. Suspend the heater only from the threaded nut

retainers or with a manufacturer provided kit. Do NOT suspend from the heater cabinet.

5.0 Hanging the

Heater

5.2 Lifting and Suspending

When the heater is lifted for suspension, support the bottom of the heater with plywood

or other appropriately placed material. If the bottom is not supported, damage could

occur. Before hanging, verify that any screws used for holding shipping brackets were

re-installed in the cabinet.
NOTE: If installation of a Model UDBP or UDBS Size 30-125 includes an optional step-

down transformer (Option CG2 or CG4), attaching the transformer bracket is part of the

suspension procedure. Follow the instructions shipped with the transformer.
When the heater is lifted for suspension, support the bottom of the heater with plywood

or other appropriately placed material. If the bottom is not supported, damage could

occur. Before hanging, verify that all screws used for holding shipping brackets were

re-installed in the cabinet.
Models UDBP and UDBS are equipped for four-point suspension. See Dimensions in

Paragraph 4.2 and the illustration in

FIGURE 5 or 6.

WARNING

Unit must be level for proper operation. Do not place or add addi-

tional weight to the suspended heater. Hazard Levels, page 2.

5.1 Weights

Before suspending the heater, check the supporting structure to be used to verify that

it has sufficient load-carrying capacity to support the weight of the unit.

Model UDBP
Size 30

45

60

75

100 125 150 175, 200 225 250 300 350 400

lbs

72 77 89 94 131 136

255

275

320 335 375 410 425

kg

33 35 40 43

59

62

116

125

145 152 170 186 193

Model UDBS
Size 30

45

60

75

100 125 150 175, 200 225 250 300 350 400

lbs

72 77 89 94 131 136

255

275

320 335 375 410 425

kg

33 35 40 43

59

62

116

125

145 152 170 186 193

Be sure the threaded

hanger rods are locked

to the hanger bars as

illustrated. Hanger

rods and hardware are

field supplied.
Recommended

maximum hanger rod

length is 6 feet (1.8M).

3/8” dia Threaded Rod

3/8” Hex Nut

3/8” Hex Nut

3/8” Lock Washers

®

FIGURE 7 - Suspending the Heater

with Threaded Rods