Form I-UDB, P/N 202658 R14, Page 15

2. Locate the 1/8” output pressure tap on the valve (See FIGURE 10, page 14). Turn

the knob or switch on the top of the valve to “OFF”. Connect a manometer to the

1/8” pipe outlet pressure tap in the valve. Use a water column manometer that is

readable to the nearest tenth of an inch.

3. Single-Stage and Two-Stage High Fire - Turn the knob or move the switch on

the top of the valve to “ON”. Remove the cap from the pressure adjusting screw

and adjust the gas train pressure to the pressure selected from the table above.

Adjust pressure by turning the regulator screw IN (clockwise) to increase pressure

or OUT (counterclockwise) to decrease pressure.

Two-Stage Low Fire - Disconnect the wire from the “HI” terminal on the gas valve

and check the low fire pressure. Turn the regulator screw to adjust the low fire outlet

pressure to the “Low Fire” pressure selected from the table. Re-connect the wire to

the gas valve.

4. Turn up the thermostat. (NOTE: On Model UDBS, depress and hold the door

safety switch.) Cycle the burner once or twice to properly seat the adjustment

spring in the valve.

Re-check the pressure(s). When the outlet pressure is right for the installation,

remove the manometer and replace the cap.

Check for leak at the pressure tap fitting.

5. With the heater operating determine that the inlet pressure to the heater for

natural gas is between 5 and 13.5 inches w.c. and for propane between 10 and

13.5 inches w.c. Take this reading as close as possible to the heater (Heaters are

equipped with gas valves that have an inlet pressure tap.) If the inlet pressure is

not within the specified range, the inlet pressure must be corrected and Steps 3

and 4 repeated.

6. Find the High Altitude Adjustment label in the plastic bag that contained these

instructions. Using a permanent marker, fill-in the appropriate information from the

tables below. Select a location for the label on the outside of the heater access

panel so that it will be conspicuous to anyone operating or servicing the unit. Be

sure the surface is clean and dry and adhere the label.

The input and/or the capacity of the heater changes with the derate. The tables below

list inputs and capacities at altitudes from sea level to 10,000 ft (3045M).

Manifold Pressure Settings by Altitude for CANADA

Altitude

Natural Gas (inches w.c.)

Propane Gas (inches w.c.)

Feet

Meters

Single-Stage and

Two-Stage High Fire

Two-Stage

Low Fire

Single-Stage and

Two-Stage High Fire

Two-Stage

Low Fire

0-2000

0-610

3.5

1.8

10.0

5.0

2001-4500 611-1373

2.8

1.5

8.1

4.1

High Altitude

Capacity Changes

BTUH Inputs and Capacities by Altitude in the UNITED STATES for Model UDBP and Model UDBS

ALTITUDE

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Normal

Input

Thermal Output

Capacity

Minimum

Input

Feet

Meters

Size 30

Size 45

Size 60

Size 75

0-2000

0-610

30000

24600

30000 45000

37350

45000 60000

49800

42000 75000

62250

52500

2001-3000 611-915 28200

23124

28200 42300

35109

42300 56400

46812

39480 70500

58515

49350

3001-4000 916-1220 27600

22632

27600 41400

34362

41400 55200

45816

38640 69000

57270

48300

4001-5000 1221-1525 27000

22140

27000 40500

33615

40500 54000

44820

37800 67500

56025

47250

5001-6000 1526-1830 26400

21648

26400 39600

32868

39600 52800

43824

36960 66000

54780

46200

6001-7000 1831-2135 25800

21156

25800 38700

32121

38700 51600

42828

36120 64500

53535

45150

7001-8000 2136-2440 25200

20664

25200 37800

31374

37800 50400

41832

35280 63000

52290

44100

8001-9000 2441-2745 24600

20172

24600 36900

30627

36900 49200

40836

34440 61500

51045

43050

9001-10000 2746-3045 24000

19680

24000 36000

29880

36000 48000

39840

33600 60000

49800

42000

Feet

Meters

Size 100

Size 125

Size 150

Size 175

0-2000

0-610

105000

88200

73500 120000

100800

84000 150000

124500

105000 175000

145250

122500

2001-3000 611-915 98700

82908

69090 112800

94752

78960 141000

117030

98700 164500

136535

115150

3001-4000 916-1220 96600

81144

67620 110400

92736

77280 138000

114540

96600 161000

133630

112700

4001-5000 1221-1525 94500

79380

66150 108000

90720

75600 135000

112050

94500 157500

130725

110250

5001-6000 1526-1830 92400

77616

64680 105600

88704

73920 132000

109560

92400 154000

127820

107800

6001-7000 1831-2135 90300

75852

63210 103200

86688

72240 129000

107070

90300 150500

124915

105350

7001-8000 2136-2440 88200

74088

61740 100800

84672

70560 126000

104580

88200 147000

122010

102900

8001-9000 2441-2745 86100

72324

60270 98400

82656

68880 123000

102090

86100 143500

119105

100450

9001-10000 2746-3045 84000

70560

58800 96000

80640

67200 120000

99600

84000 140000

116200

98000