English – KEYENCE SL-CHG Series User Manual
Page 46
Chapter 4 Checklist
4-4
4
English
ENGLISH
❏
The test piece can be detected regardless of its location as long as it is in the detection zone.
❏
If the SL-R11G restart interlock function is enabled, when the test piece is removed, confirm that
the bar LEDs on the SL-CHG light up green, the output status indicator lights up red, and the SL-
R11G interlock indicator lights up yellow.
❏
When in the restart interlock state, the start/restart input causes the output status indicator to
change to green, and the SL-R11G interlock indicator to turn off.
❏
If the SL-R11G start interlock function is enabled, confirm that the bar LEDs lights up green, the
output status indicator lights up red, and the SL-R11G interlock indicator lights up yellow when the
power of the SL-CHG is turned on with no object in the detection zone.
❏
In addition, the output status indicator changes to green and the SL-R11G interlock indicator turns
off when there is a start/restart input while in the start interlock state.
Move the test piece for detection confirmation as illustrated in the figure below.
Star
t
Stop
3. Operation Test with the Machine Operating
This test confirms that the machine stops its operation.
❏
Place the test piece in the detection zone or protection zone of the SL-CHG. It is recommended to
try three locations: near the transmitter, near the receiver, and the central area of the detection
zone. The machine must stop immediately as soon as the test piece is placed.
❏
The machine must remain stopped as long as the test piece is in the detection zone.
❏
The machine will not operate when the SL-CHG Series power supply has been interrupted.
❏
The overall response time of the machine, including the response time of the SL-CHG and the time
it takes for the machine to stop, must be shorter than the overall response time T used in the
calculation of safety distances (
See “2-2 Safety Distances” (
➮page 2-4)).
4. Test Results Confirmation
❏
If the SL-CHG or the machine to which the SL-CHG has been installed fails any part of the above
test, operation should be ceased until satisfactory test results are obtained.
❏
A record of the test results must be maintained.
WARNING
If the SL-CHG does not function as described in the test procedure, do not attempt
to operate the machine to which the SL-CHG has been installed. Such an operation
may lead to the serious harm, including a serious injury or death of the machine
operator.