Precautions when installing

z

Attaching the coupling

The recommended tightening torque when installing the adapter

to the main body of the sensor is 20 N•m. It is recommended to

apply grease to the G3/4 screw part in order to avoid scorching.
z

Grounding of metal parts

The metal parts of the main body, the internal circuits 0 V are insulated.
z

Other precautions

• Regardless of whether the power

of the device is ON or OFF, do not

touch the main part of the

pressure detector, if the if the

pressure detector is touched,

damage may occur due to static

electricity.

• If using a non-conductive liquid such as oil, and plastic piping

are used, the risk of an offset change will become greater. In

such a case, it is recommended to ground the metal housing.

• In the case that noise causes malfunction, grounding the

metal housing may improve performance.

• After installation, conduct an atmospheric correction by

making the applied pressure the same as regular room

pressure. (Refer to page 10)

• When there is condensation,

separate the sensor from cooling

pipe by at least 30 cm using the

connecting pipe.

Cooling pipe

30 cm or more