Medium temperature -20 to +100°C (no freezing/condensation)
*3 *6
Power supply
voltage
10-30 VDC, Ripple (P-P): 10% max,
Class 2 or LPS
Current
consumption
50 mA or less (when 24 V: 32 mA or less, when
12 V: 48 mA or less. Excluding output)
*4
Display method
4 column digital LED red/
Vertical inversion display possible
Operation display
light
Operation indicator (output 1) (orange)
Operation indicator (output 2) (orange)
Hysteresis
During hysteresis mode: variable
(Difference between switch-on point and
switch-off point is hysteresis)
During window mode: fixed (0.5% of F.S.)
Response
Control
output
Selectable from 3 to 5000 ms
Analog
output
As above + 2 ms (90% response)
Output 1
control output
NPN/PNP open collector (Selectable)
30 V or less, Max. 250 mA
Residual voltage for the Main Unit is
1 V or less, N.O./N.C. selectable
Output 2
(replace
-ment
type)
Control
output
Analog
output
4-20 mA, maximum load resistance 500
Ω
(When the electric voltage is more than 20 V)
*5
Environmental
resistance
Ambient
temperature -20 to +80°C (no freezing/condensation)
*6
Relative
humidity
35 to 85% RH (no condensation)
*6
Vibration
IEC60068-2-6 20 G (10 to 2000 Hz
In each direction of X, Y, Z for 2 hours)
Shock
IEC60068-2-27 50 G (11 ms
In each direction X, Y, Z 3 times)
Enclosure
protection
IP67
Ra
ting
O
ut
put