Data update time

The data update time for cyclic communication is shown below.

Maximum data processing time = (1) + (2) + (3) + (4)
(1)PROFIBUS DP master data update time
(2)Network data update time
(3)Data update time between the DL-PD1 and sensor amplifiers

(4)Sensor amplifier response time

For (1) and (2), see manuals for each model.
For (4), refer to the User's Manual of each sensor amplifier connected to the DL-PD1.

Number of connected

sensor amplifiers

Control output/Comparator value

Calculation function

OFF

Calculation function

ON

1

9ms

12.5ms

2

11ms

15.5ms

3

15ms

21.5ms

4

17ms

24.5ms

5

21ms

30.5ms

6

23ms

33.5ms

7

27ms

39.5ms

8

29ms

42.5ms

9

33ms

48.5ms

10

35ms

51.5ms

(4)

(3)

(2)

(1)

DL-PD1

Sensor amplifier

PROFIBUS DP master