Profibus dp master address, Manufacturer id, Parameterization -8 – KEYENCE DL-PD1 User Manual
Page 34: Diagnostic function -10, Station status 2, Station status 3, 4 diagnostic function, Execu ting communi cat ion, The parameter is not assigned

3-4
Diagnostic Function
3-12
- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT-70A) -
Execu
ting Communi
cat
ion
3
Station status 2
*1 This bit is updated only when another diagnosis message is updated, too.
Station status 3
PROFIBUS DP master address
The PROFIBUS address of PROFIBUS DP master is stored in Octet 4. When the value
is FF
H
, the parameter is not assigned.
Manufacturer ID
Codes unique for the DL-PD1 status are stored in Octet 5 and 6.
Octet
bit
Content
2
0
Set the DL-PD1 parameter again.
1
A diagnosis message is present. The DP slave does not operate until the problem is eliminated.
(Static diagnosis message)
2
(1 fixed)
3
The watchdog is enabled.
4
The DP slave is in "FREEZE" state.
*1
5
The DP slave is in "SYNC" state.
*1
6
(0 fixed)
7
The DP slave is disabled.
Octet
bit
Content
3
0
:
6
(0 fixed)
7
Diagnosis messages exceed the maximum amount that can be stored. Increase the storing memory.
Octet
Content
Value
5
Manufacturer ID is stored. (high byte)
0D
H
6
Manufacturer ID is stored. (low byte)
FD
H