1 troubleshooting, Indicator specifications, I&m -34 freeze/sync/clear command -35 – KEYENCE DL-PD1 User Manual
Page 60: Troubleshooting -2, Troubleshooting, Appe ndi x

4-2
- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT-70A) -
Appe
ndi
x
4
4-1
Troubleshooting
Indicator Specifications
The communication status of PROFIBUS DP can be checked by checking the DL-PD1
indicators.
LED display during
normal operation
Station Failure Indicator (OFF)
Bus Failure Indicator (OFF)
Data Exchange Indicator (green)
Sensor amplifier Communication Indicator (green)
SF
BF
DE
D-bus
State
Solution
OFF
OFF
Green
Green
Operating properly.
Red
Red
OFF
OFF
Starting up
The unit enters normal state after startup
operation is complete.
Red
Red
OFF
Red
System error
Turn the power on again. If the unit does not
recover, please contact your nearest
KEYENCE office (addresses are listed at the
back of this manual).
Red
*
OFF
Green
(Flashing) Starting up
The unit enters normal state after startup
operation is complete.
Red
An error occurred in the
internal system.
Check that the DL-PD1 is properly connected
to the sensor amplifier and turn the DL-PD1 on
again.
Red
(Flashing)
Communication is tentatively
impossible.
Check that there is no noise generation source
around the DL-PD1. (If the cause is removed,
normal condition is automatically recovered.)
Red
(Flashing 4
times
repeatedly)
•
An incompatible sensor or
a foreign sensor amplifier
(i.e., one that cannot be
intermixed) is connected.
•
A current limitation error
has occurred.
Confirm the sensor amplifier configuration.
Red
OFF
Green
Green
The station address setting
switch was changed during
operation.
If it was not an intentional change, recover the
setting. Normal condition is automatically
recovered.
Red
(Flashing)
OFF
Green
Green
Warning information is
notified.
Check the sensor condition.
OFF
Red
(Flashing)
OFF
*
Wait Prm state timeout of
DL-PD1
ChkCfg state timeout of
DL-PD1
•
Check that the hardware configuration on the
configuration software coincides with the
actual configuration.
•
Check that the station address setting on the
configuration software coincides with the
station address setting on the rotary switch
of the DL-PD1.
•
Using the configuration software, check that
the DL-PD1 Parameters are correctly set.
OFF
OFF
Green
(Flashing)
*
Starting up
The unit enters normal state after startup
operation is complete.
OFF
OFF
OFF
OFF
Power OFF
Check that the DL-PD1 is connected to the
power source.