Vender parameter, 3 parameterization, Execu ting communi cat ion – KEYENCE DL-PD1 User Manual
Page 31: Unique parameters for dl-pd1

3-3
Parameterization
3-9
- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT-70A) -
Execu
ting Communi
cat
ion
3
Vender parameter
Unique parameters for DL-PD1
: Default value
Octet
Name
Description
Value
11
Reserved
-
1 (fixed)
12
Data Format
Selects data storage format when
sending/receiving 2 bytes or larger data.
0: Intel (little endian)
1: Motorola (big endian)
13
Extended Diagnosis
Selects whether to include information
other than standard diagnosis into slave
diagnosis.
0: Disable
1: Enable
14
Indicate error slot
[Sensor Amplifier]
Selects the sensor amplifier as a target
for slave diagnosis. If the sensor
amplifier is set as a target, set bit
corresponding to the slot number.
"Diagnostic Function" (page 3-10)
(Default value: 1111 1111
B
)
15
(Default value: 1111 1110
B
)
Slot 0 is fixed to 0.
16
Indicate warning slot
[Sensor Amplifier]
Selects whether to include warning
information into slave diagnosis
information. If so, set bit corresponding
to the slot number.
(Default value: 0)
17
(Default value: 0)
18
Reserved
-
0 (fixed)
bit
7
:
:
0
Slot 15
Slot 8
bit
7
:
:
0
Slot 7
Slot 0
bit
7
:
:
0
Slot 15
Slot 8
bit
7
:
:
0
Slot 7
Slot 0