4 message communication 3-39 – KEYENCE DL-EP1 User Manual
Page 67
3-4 Message Communication
3-39
3
C
om
m
uni
ca
tin
g
w
ith FD
-M
H
Se
ries
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (FD-MH) -
Group3
0364H
(868)
Free range
analog
upper limit
*10
Indicates the free range analog upper limit.
Parameter range:
FD-MH10A: 0.0 to 30.0
(Initial value: 10.0, settable unit: 0.1)
FD-MH50A: 0 to 100
(Initial value: 50, settable unit: 5)
FD-MH100A: 0 to 200
(Initial value: 100, settable unit: 10)
FD-MH500A: 0 to 1000
(Initial value: 500, settable unit: 50)
R/W
DINT
0365H
(869)
Free range
analog
lower limit
*10
Indicates the free range analog lower limit.
Parameter range:
FD-MH10A: 0.0 to 30.0
(Initial value: 0.0, settable unit: 0.1)
FD-MH50A: 0 to 100
(Initial value: 0, settable unit: 5)
FD-MH100A: 0 to 200
(Initial value: 0, settable unit: 10)
FD-MH500A: 0 to 1000
(Initial value: 0, settable unit: 50)
R/W
DINT
0366H
(870) to
037FH
(895)
(Reserved for system)
Group4
0380H
(896)
Group4 Entry
count
Indicates the group 4 entry count.
Parameter range: 29
R
DINT
0381H
(897)
(Reserved for system)
0382H
(898)
Detection
mode
Indicates the Detection mode.
Parameter range: 0 to 4
0: F-1 (initial value)
1:F-2
2:F-3
3:A-1
4:A-2
R/W
DINT
0383H
(899)
(Reserved for system)
0384H
(900)
Response
time
Indicates the response time.
Parameter range: 0 to 6
0:0.5s
1:1.0s
2:2.5s
3:5.0s (initial value)
4:10.0s
5:30.0s
6:60.0s
R/W
DINT
0385H
(901)
Display
averaging
*11
Indicates the display averaging.
Parameter range:
0.0 to 10.0 (initial value: 1.0, settable unit: 0.5)
R/W
DINT
0386H
(902)
Output 2
timeout time
Indicates the output 2 timeout time.
Parameter range: 1 to 99 (initial value: 10)
R/W
DINT
0387H
(903)
Integration
direction
Indicates the integration direction.
Parameter range: 0 to 1
0: Increment (initial value)
1: Decrement
R/W
DINT
Class
Attribute
ID
Name
Description
Attribute
Data
Type