4 message communication 3-33 – KEYENCE DL-EP1 User Manual
Page 61

3-4 Message Communication
3-33
3
C
om
m
uni
ca
tin
g
w
ith FD
-M
H
Se
ries
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (FD-MH) -
Attributes
Instance
ID
Attribute
ID
Name
Description
Attribute
Data
Type
00H
64H
(100)
Status
Indicates the status of this unit and connected
sensor amplifier.
bit0: DL-EP1 Error Status
Bit 1 to bit 13: Reserved for system
bit14: Warning Status
bit15: Error Status
R
WORD
65H
(101)
Sensor Error
Status
Indicates the error status of the connected
sensor amplifiers. If an error occurs, the bit of the
corresponding ID number of amplifier is turned
to ON.
Bit 0 to bit 9: ID number 1 to ID number 10
Bit10 to bit 15: Reserved for system
R
WORD
66H
(102)
Warning
Status
(Unassigned)
R
WORD
67H
(103)
Reserved for system
68H
(104)
Current
Value 0
Property
Indicates the status of current value 0 of each
amplifier. If the current value 0 is “Over Range",
“Under Range", or "Invalid", the bit
corresponding to the ID number is turned ON.
Bit 0 to bit 9: ID number 1 to ID number 10
Bit10 to bit 15: Reserved for system
R
WORD
69H
(105)
Current
Value 1
Property
(Unassigned)
R
WORD
6AH
(106) to
6BH
(107)
Reserved for system
6CH
(108)
Error ID
Number
Indicates the ID number of the unit having error.
Parameter range: 0 to 10 (initial value: 0)
R
UINT
6DH
(109)
Error Code
Indicates the error code that is happening.
Parameter range: 0 to 65535 (initial value: 0)
R
UINT
6EH
(110)
Warning ID
Number
(Unassigned)
R
UINT
6FH
(111)
Warning
Code
(Unassigned)
R
UINT
70H
(112) to
73H
(115)
Reserved for system
74H
(116)
Output1
Indicates the output 1 status of each sensor
amplifier. When output 1 is output, the bit
corresponding to the ID number of the sensor
amplifier is turned ON.
Bit 0 to bit 9: ID number 1 to ID number 10
Bit10 to bit 15: Reserved for system
R
WORD