About the Home Tab
Use the Home tab to view active alarms, the load status of the Rack PDU, and the
most recent Rack PDU events.
The Overview view
Path: Home > Overview
The top of the Overview indicates the alarm status. If one or more alarms are present,
the number and type of alarms are indicated with a link to the
Alarm Status
view,
where you can view descriptions of each alarm. If no alarms exist, the Overview
displays, “No Alarms Present.”
In the
Load Status
area, view the load for the device in kW and for the phases
in Amps, as applicable. The green, yellow, and red meter shows the current load
status: normal, near overload, or overload. Note that if a low load threshold was
configured the meter will also include a blue segment to the left of the green. Hover
over the colors to view the configured load thresholds.
Click
More
to go to the
Device Manager
tab to configure thresholds and to view and
manage peak load information.
In the device parameters area, view the name, contact, location, current rating, type of
user account accessing the Rack PDU, and the amount of time the Rack PDU has
been operating since the last reboot from either a power cycle or a reboot of the
Management Interface. [For more information, see
In the
Recent Device Events
area, view, in reverse chronological order, the events
that occurred most recently and the dates and times they occurred. A maximum of five
events are shown at one time. Click
More Events
to go to the
Logs
tab to view the
entire event log.