USER’S GUIDE

Mete

red Rac

k

PDU

12

 Function button

• To manually display the current for each phase,

repeatedly press the button. The current displays
for 30 seconds or until you press the button again.
(This functionality is not available for single-phase
Rack PDUs.)

• To display the IP address, press and hold for five

seconds until

IP

appears; then release. On the

LED display, the address will appear two digits at
a time and then the cycle will repeat.

• To invert the display, press and hold for ten

seconds until the

AA

pattern appears. Continue

holding the button until AA is oriented as desired
then release the button.

 10/100 Base-T Connector

Port for connecting the Rack PDU to the network.

 10/100 LED

See

10/100 LED

.

 Network Status LED

See

Network Status LED

.

 Temp/Humidity sensor port

Port for connecting a Rack PDU Temperature
Sensor (G853N) or a Rack PDU Temperature/
Humidity Sensor (H621N).

 RJ-45 Serial Port

Port for connecting the Rack PDU to a terminal
emulator program for local access to the command
line interface. Use the supplied serial cable.

 Reset Button

To restart the interface of the Rack PDU without
affecting the outlets, press and release the Reset
button.

Item