Environment
Configuring Temperature and Humidity Sensors
Path: Environment > Temperature & Humidity
Through the
Temperature & Humidity
page, when you have a temperature or a
temperature and humidity sensor connected to the Rack PDU, you can set thresholds
for Warning and Critical alarm generation (see
type of alarm).
For temperature:
• If the high temperature threshold is reached, the system generates a Warning alarm.
• If the maximum temperature threshold is reached, the system generates a Critical
alarm.
Similarly, for humidity:
• If the low humidity threshold is reached, the system generates a Warning alarm.
• If the minimum humidity threshold is reached, the system generates a Critical alarm.
To configure temperature and humidity sensors:
1 . Enter values for minimum, maximum, high, and low thresholds.
2 . Enter
Hysteresis
values. (See
for details.)
3 . Enable alarm generation as desired.
4 . Click
Apply
.
Click the thermometer symbol in the upper right corner to toggle
between fahrenheit and celsius.