Communication
4-25
completely submerged. Refer to the National Fire Protection
Association (NFPA) Standard 70 National Electrical Code
(NEC) Article 250 for detailed instructions on proper
grounding when an 8-foot vertical depth is not available.
Mounting the Lightning Protection Module
The next step in establishing telephone service is mounting the
lightning protection module to the service pedestal. Mount the
module as follows:
1. Remove the front cover from the pedestal.
2. Use the screws included with the lightning protection module to
mount the module on the pedestal at least 12 inches above the
ground surface and next to or 6 to 8 inches below the network
interface box.
Positioning of the lightning protection module and network interface box in
the pedestal