Parameters and Function Codes
Chapter 4
T Parameters
Parameter
Number
Description
Default
Value
Modify
Root
Lower
Limit
Upper
Limit
T01
Fault-To-Bypass
0: Disable
1: Enable
0
ON
0
1
T02
Fault-To-Bypass Delay
3
ON
0
60
T03
Fault-To-Bypass Delay When Starting
the Motor (0...60s)
60
ON
0
60
T04
Fault-To-Bypass Minimum Frequency
0...Rated Frequency (Hz)
5
ON
0
Rated
Frequency
T05
Auto Restart After Input Supply Power Loss
0: Disable
1: Enable
0
ON
0
1
T06
Input Supply Power Loss Time for
Auto Restart (0...20s)
20
ON
0
20
T07
Local Frequency Command Selection
0: Digital
1: Analog
0
ON
0
1
T08
Remote Frequency Command Selection
1: Analog
2: 4-Step Speed
4: Communication Port
1
ON
1
4
T09
Frequency Step For Accel or Decel
1
ON
1
Rated
Frequency
T10
Exit Config Environment Password
555
OFF
T11
Automatic Bypass-To-Drive or
Drive-To-Bypass Selection
T12
PID Parameter Settings
P
0.01
ON
0
32767
I
0.01
ON
0
32767
D
0
ON
0
32767
D Gain
0
ON
0
32767
T13
4-Step Variable Speed
(available only when T8=2)
Speed 1
10
ON
0
Rated
Frequency
Speed 2
20
ON
0
Rated
Frequency
Speed 3
30
ON
0
Rated
Frequency
Speed 4
40
ON
0
Rated
Frequency